Table of Contents INTRODUCTION ......................... 6 Welcome ................................6 Future Products Group (FPG) ........................6 Guidance and Help ............................. 6 Warranty ................................6 Warranty Period ............................6 Liability Exceptions ............................. 7 Specific Exclusions ............................. 7 Assessment ..............................7 Time Limit ..............................7 Caution ...............................
Page 4
Exterior ................................16 Louvers ..............................16 Painted and Metal Surfaces ........................16 Glass ................................ 16 Interior................................17 Side Glass ..............................17 Shelf Trays ............................... 17 Spillage Tray ............................. 17 Base Trays and Air Baffles ........................17 Back Plates ............................... 17 Cleaning the Base Cavity .........................
Page 5
Automatic Condensate Removal, (ACR) Unit ..................27 ACR Fault Finding Guide ......................... 28 Condensate Element Replacement ......................28 MPXPRO Functions & Indications ......................29 FPG Settings ............................29 MPXPRO Parameters ..........................30 MPXPRO Connections ..........................32 Mains Lead ..............................32 Lead Replacement ...........................
INTRODUCTION Welcome VISAIR+ CABINETS INTRODUCTION Future Welcome to the world of FPG! Our products are designed and engineered to Products give you the optimal performance that you deserve with innovative visual Group (FPG) merchandising appeal. We are confident that you will be delighted with your state of the art Inline Visair food service cabinet, and that it will become a valued appliance in your store.
Fair wear and tear. Assessment The liability under this warranty is dependent on an assessment by FPG, to determine the defect in workmanship or materials. Time Limit FPG does not guarantee that any service to be performed under this warranty will be carried out within any particular time limit.
OPERATION Cabinet Layout VISAIR+ CABINETS OPERATION Visair Cube This is a stand-alone, open fronted cabinet, with glass side panels and a top fluorescent light. Various shelf configurations are available to accommodate different package sizes. Cabinets are fully self-contained, with an integral refrigeration unit.
Controls & Indicators VISAIR+ CABINETS OPERATION Power Switch The main power switch is mounted in the and Indicator top of the front base panel, on the right Lamps hand side. This is the only operator control, and it switches the lighting and refrigeration on and off.
Preparation VISAIR+ CABINETS OPERATION Shelf Location All shelves are adjustable in height and can easily be moved up or down, to and Ticketing match product size. The front edges of the shelves are profiled to carry ticketing/labels. Shelf To alter the shelf position, slide the brackets Adjustment upwards and disengage them from the support pillar.
Preparation cont. VISAIR+ CABINETS - OPERATION Switch Power Turn on the power switch, the compressor will run, and the cabinet temperature will begin to fall. The temperature controller is pre-set to maintain the cabinet temperature at 2 - 4C. It should not need adjustment.
Routines VISAIR+ CABINETS OPERATION After Hours Ideally, cabinets should not be turned off after hours or at night. If the cabinet is turned off, transfer the products to a cool store. When the cabinet is turned on again, allow it to run for 30 minutes before returning the chilled products.
TROUBLE SHOOTING FAULT POSSIBLE CAUSE REMEDY The mains isolating switch on Turn isolating switch circuit the wall, circuit breaker or fuses breaker or fuses on are off at the power board The power switch on the cabinet Turn the power switch ON Cabinet does not is OFF operate/start...
TROUBLE SHOOTING continued Boil-off /Pump If the cabinet shuts down and the Boil-off/Pump fail LED fault light is lit, then Failure LED either the condensate pump has failed or the boil-off element thermal cut-out illuminated will have tripped. Thermal Cut- Check if the probe in the boil-off tank is dirty and needs cleaning (a dirty probe out Tripped can complete a circuit to earth causing the unit to think water is still present and...
TROUBLE SHOOTING continued Lights not When a cabinet alarm condition is present, the cabinet lights will go out to alert working staff of the alarm condition. To determine the cause of the alarm condition, check the Carel controller display and the LED status indicator lamps. Alarm code “IA”...
CLEANING Cautions VISAIR+ CABINETS CLEANING Power ALWAYS TURN THE POWER SUPPLY OFF BEFORE CLEANING. Water THIS UNIT IS NOT WATERPROOF. DO NOT USE A WATER JET SPRAY TO CLEAN THE INTERIOR OR EXTERIOR OF THIS CABINET. Exterior VISAIR+ CABINETS CLEANING Louvers Use a vacuum cleaner to remove dust and fluff from the ventilation louvers on the top of the cabinet.
Interior VISAIR+ CABINETS CLEANING Side Glass The inside surfaces of the side panels are most easily cleaned after the products and shelves have been removed. Shelf Trays The shelf trays are easily lifted off for cleaning. The complete shelf module can also be removed by lifting it vertically, to disengage the...
Interior cont. VISAIR+ CABINETS - CLEANING Cleaning the The cabinet base is mounted on runners, Base Cavity and can be pulled forwards to access the base cavity. Sweep out, or use a vacuum cleaner, to remove any debris. A Wet-and-Dry vacuum cleaner should be used, since there is likely to be some water in the bottom.
Interior cont. VISAIR+ CABINETS - CLEANING Cooling Coil With the back plates removed, the cooling coil is and Probes exposed. No cleaning is normally required, but if there is any debris visible, carefully remove it with a vacuum cleaner. Be very careful not to bend or distort the fins of the cooling coil, as this would reduce the airflow.
Mandatory Cleaning Routines VISAIR+ CABINETS CLEANING Warning It is mandatory to have the radiator fins cleaned periodically, by a refrigeration engineer. (see Servicing section). Failure to carry out routine cleaning/servicing schedules will void the warranty on the refrigeration equipment. To maintain optimum performance, cleaning must be regular and thorough. It is recommended that a schedule of cleaning operations should be drawn up.
INSTALLATION Regulations VISAIR+ CABINETS INSTALLATION Compliance It is very important that your food cabinet is installed correctly and is operating with Local properly before use. Installation must comply with local electrical, health & Requirements safety and hygiene requirements. Setting Up VISAIR+ CABINETS INSTALLATION Unpacking...
Setting Up cont. VISAIR+ CABINETS - INSTALLATION Power Supply Each cabinet is fitted with a three-pin IEC connector and a and Earthing three metre mains lead. If the cabinet is to be hard wired, this must only be done by a suitably qualified person.
SERVICING Electrical Protection VISAIR+ CABINETS SERVICING Circuit Breaker The lighting circuit is protected by a circuit breaker, located on the control gear chassis. The circuit breaker is accessible through a hole in the side of the chassis. If the breaker cannot be reset, call an electrician to check the circuits.
Refrigeration Equipment VISAIR+ CABINETS SERVICING Caution DO NOT attempt to service the refrigeration equipment without isolating the cabinet from the mains supply. Equipment The compressor, control gear chassis and Chassis condensate pump are mounted in the base of the cabinet. Unscrew the front panel to gain access.
Refrigeration Equipment cont. VISAIR+ CABINETS - SERVICING Evaporator Fan The fan deck is not fixed in place, and can Replacement be unplugged to replace a faulty fan. The fan speed is electronically programmed, so the correct spare must be used. Evaporator Coil The evaporator coil and accumulator are accessed by removing the inside back...
Refrigeration Equipment cont. VISAIR+ CABINETS - SERVICING Air Ducts and All air ducts and grills must be regularly Grills vacuumed, to keep them free of dust and fluff. This is best done with the condenser fans withdrawn, and after cleaning the radiator with compressed air.
Refrigeration Equipment cont. VISAIR+ CABINETS - SERVICING Condensate The pump is activated by a float switch in Pump the inlet filter module, and also provides a monitor signal to the MPXPRO controller. If the pump is not working, make sure that the float switch is assembled with the magnet towards the...
Refrigeration cont. VISAIR+ CABINETS - SERVICING ACR Fault First check if the condensate water level probe in the ACR tank is dirty and Finding Guide needs cleaning (a dirty probe may either fail to detect water, or give a false indication of water) clean if required.
Refrigeration cont. VISAIR+ CABINETS - SERVICING MPXPRO Parameters Continued on next page Part No. 20862 Rev. G February 2015 - 30 - Visair+ Chilled Cabinets...
Refrigeration cont. VISAIR+ CABINETS - SERVICING MPXPRO Parameters continued MPXPRO Connections Mains Lead VISAIR+ CABINETS SERVICING Lead If damaged, the mains lead must ONLY be replaced by a qualified service Replacement person. Part No. 20862 Rev. G February 2015 - 32 - Visair+ Chilled Cabinets...
SPECIFICATIONS Mechanical VISAIR+ CABINETS SPECIFICATIONS CABINET MODEL IN-M11C- IN-M11C- IN-M11C- B003 B004 B007 Height mm 1479 1479 Width mm 1096 1096 Depth mm Dry Weight kg Cabinet Well Material Powder-coated Powder-coated steel steel Number of Shelf Modules 1.5 (shelves) 0.8 (shelves) Display Area m + 0.4 (base) + 0.4 (base)
Controller Settings VISAIR+ CABINETS SPECIFICATIONS Changes from The following table specifies the controller settings which differ from the Carel Carel Defaults default values. Parameters not listed in this table should remain at the default values specified in the MPXPRO Parameters listed in the Servicing section. Carel MPX PRO Settings CABINET MODEL Parameter...
Number the label fixed to the control panel. This serial number will enable FPG to trace details of the build specification of your particular cabinet, and hence ensure that spare parts are fully compatible. To satisfy warranty conditions, and ensure optimum performance, use only FPG supplied spare parts.