Heatilator CD4236IFTR Installation Manual page 22

Hide thumbs Also See for CD4236IFTR:
Table of Contents

Advertisement

Top Vent - Horizontal Termination - (continued)
One Elbow
ELBOW HEAT SHIELD
(Required when V
1
Figure 4.11
Two Elbows
H
2
Figure 4.12
22
Heatilator • CD4236IFTR, CD4236IFTLR, CD4842IFTR, CD4842IFTLR Installation Manual • 2511-980 Rev. M • 8/21
= 2 ft. or less)
H
1
Note: For corner installations: A 6 in.
(152 mm) section of straight pipe may
need to be attached to the appliance
before a 90º elbow, to allow the vent
pipe to clear the top standoffs.
INSTALLED
HORIZONTALLY
WARNING! Risk of Fire! Elbow heat shield required
when V
= 2 ft. or less. Clearances to combustibles
1
must be maintained. See Section 5.A.
1/2 ft.
V
1
1-1/2 ft.
H
1
V
Minimum
H
1
1
Elbow only
2 ft
152 mm
6 ft.
1 ft.
305 mm
11 ft.
457 mm
18 ft.
2 ft.
610 mm
25 ft.
V
+ H
= 40 ft. (12.2 m) Maximum
1
1
H
= 25 ft. (7.6 m) Maximum
1
Note: For corner installations: A 6 in.
(152 mm) section of straight pipe may
need to be attached to the appliance
before a 90º elbow, to allow the vent
pipe to clear the top standoffs.
V
Minimum
H
+ H
1
1
Elbow only
2 ft
1/2 ft.
152 mm
6 ft.
1 ft.
305 mm
11 ft.
1-1/2 ft.
457 mm
18 ft.
2 ft.
610 mm
25 ft.
V
+ H
+ H
= 40 ft. (12.2 m) Maximum
1
1
2
H
+ H
= 25 ft. (7.6 m) Maximum
1
2
V
1
Maximum
610 mm
1.8 m
3.4 m
5.5 m
7.6 m
Maximum
2
610 mm
1.8 m
3.4 m
5.5 m
7.6 m