Samsung CH070EAV1 Service Manual page 72

System air conditioner
Table of Contents

Advertisement

4-5-13 Compressor start error
1. Checklist :
1) Is the connection of cable for the compressor and power?
2) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after power off.
Is the restart error occurred again?
Is the interphase resistance value of
compressor(u↔v, v↔w, w↔u) normal?
Is the compressor body and
interphase resistance insulated?
Is the connection cable for the
compressor and power terminal normal?
Exchange the PCB.
4-32
�es
�es
�es
�es
No
Terminate the service.
No
Exchange the compressor.
No
Exchange the compressor.
No
Correct the cable connection.
Samsung Electronics

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents