Siemens RUGGEDCOM RS920W Installation Manual page 37

Wireless serial device server
Hide thumbs Also See for RUGGEDCOM RS920W:
Table of Contents

Advertisement

RUGGEDCOM RS920W
Installation Guide
Test
IEC 61000-4-16
IEC 61000-4-17
IEC 60255-5
IEEE 1613 (C37.90.x) EMI Immunity Type Tests
NOTE
The RS920W meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for
copper ports.
IEEE Test
C37.90.3
C37.90.2
C37.90.1
C37.90
EMI and Environmental Type Tests
Description
Mains Frequency Voltage
Ripple on DC Power Supply
Dielectric Strength
HV Impulse
IEEE 1613
Clause
9
ESD
8
Radiated RFI
7
Fast Transient
Oscillatory
6
HV Impulse
Dielectric
Strength
DC Power ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
AC Power ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
Signal ports
30 V Continuous, 300 V for 1 s
DC Power ports
30 V Continuous, 300 V for 1 s
DC Power ports
Signal ports
2 kVAC (Fail-Safe Relay output)
DC Power ports
AC Power ports
Signal ports
5 kV (Fail-Safe Relay Output)
DC Power ports
AC Power ports
Description
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
DC Power ports
AC Power ports
Earth ground ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
Test Levels
Severity Levels
10%
1.5 kVDC
2 kVDC
5 kV
5 kV
Test Levels
+/- 8 kV
+/- 15 kV
35 V/m
+/- 4 kV @ 2.5 kHz
+/- 4 kV
+/- 4 kV
+/- 4 kV
2.5 kV common mode @ 1MHz
2.5 kV common and
differential mode @ 1MHz
2.5 kV common and
differential mode @ 1MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kVAC (Failsafe Relay)
1.5 kVDC
Chapter 6
Certification
3
3
4
4
3
31

Advertisement

Table of Contents
loading

Table of Contents