System Configuration - ClimateMaster Trilogy Variable (VE) Series Installation, Operation & Maintenance Instructions Manual

Table of Contents

Advertisement

Variable ( VE ) Series IOM - 60Hz HFC-410A
Trilogy
®
R e v i s i o n D a t e : 2 2 D e c e m b e r , 2 0 2 1

System Configuration

Configuring The iGate
The first step after installing the iGate
to configure the settings for the various devices that are being
connected. This can be done through the myUplink App or
Service Tool. The various configuration options are detailed
below and in the iGate Connect IOM.
The Unit Configuration settings allow the installer to configure
the thermostat to the installed equipment.Unit Configuration
is only necessary when replacing a unit controller. The Unit
Configuration settings are programmed at the factory when
the unit is built.
Configuration Setting
Heat Pump Family
Heat Pump Size
Blower Type
Threshold Configuration
This section configures the temperature, time, and capacity thresholds associated with the heating, cooling, and hot water (if
applicable) equipment. You must configure the Equipment settings before setting the thresholds. Only the applicable threshold
settings will be displayed.
System Setting
Compressor Anticipator
Cooling Hot Water
Cut Out
Heating Hot Water
Cut Out
Auxiliary Heat Dead-Band
Cooling Hot Water
Cut Out Offset
Heating Hot Water
Cut Out Offset
34
Connect Thermostat
®
Connect thermostat is
®
Description
Select the family of heat pump.
Select the unit model.
Select the blower type.
Configures the sensitivity of the thermostat to the space temperature. A
lower setting will cause the unit to respond more rapidly to changes in space
temperature. A higher setting will cause the unit to respond more slowly to
changes in space temperature.
Determines the point at which the space cooling demand outpaces the ability of
the potable water heating mode to accept the heat of rejection from the cooling
mode when both are active at the same time. At this setting and above the heat
of rejection from the cooling mode will be sent to the source (ground loop).
Potable water heating normally takes priority over space heating. This setting
determines the point at which the space heating demand will take priority over
the potable water heating demand.
Configures the amount of space temperature droop allowed from the heating
setpoint at maximum unit capacity before allowing auxiliary heat for space
heating.
This setting establishes the maximum acceptable space temperature rise
during the cooling mode while the heat from the space is being rejected into
the potable hot water. If the space temperature rises more than this amount,
the potable water heating mode will be terminated and the cooling mode will
reject the heat from the space to the source (ground loop).
This setting establishes the maximum acceptable space temperature drop
during the potable hot water mode before the unit switches to the space
heating mode. If the space temperature drops more than this amount, the
potable water heating mode will be terminated and the space heating mode will
be activated.
G e o t h e r m a l H e a t i n g a n d C o o l i n g
Capacity Configuration
Range for the capacity settings will depend on model selection.
Configuration Setting
Minimum Heating Capacity
Maximum Heating
Capacity
Minimum Cooling Capacity
Maximum Cooling
Capacity
Description
Description
Configures the minimum unit heating
capacity. When the space requires a
heating capacity below this setting the unit
will cycle off.
Configures the maximum unit heating
capacity. When the space requires a
heating capacity above this setting the unit
will call for auxiliary heat (if applicable).
Configures the minimum unit cooling
capacity. When the space requires a
cooling capacity below this setting the unit
will cycle off.
Configures the maximum operational unit
cooling capacity.
Range/Options
Default
1 to 10
5
70% to 100%
100%
70% to 100%
90%
0.0°F to 5.0°F
1.0°F
0.5°F to 1.5°F
0.5°F
0.5°F to 1.5°F
1.0°F