Load Options; Battery Options - AEG PROTECT RCS Operation Manual

Table of Contents

Advertisement

8.2.3
TCP/IP Communication – Plug-in type
This option includes a NCS board connected to A71 (RS232 board) and allowing TCP/IP communication with the
GCAU control board. The Modbus RTU interface connection option needs to be installed in the charger so that the
TCP/IP communication can be implemented.
The board provides the following protocols: HTTP (Web navigator), SNMP, connection to Winsparc via a network,
Modbus TCP.
How to instal and activate this option on the control card : Refer to the option installation manual
For more details please refer to separate NCS manual document.

8.3 LOAD OPTIONS

8.3.1
Blocking diode – Factory integrated type
This diode is used to allow the charger to be connected to a second changer and prevents any reverse
current to flow inside the charger.
8.3.2
Supplementary protective devices – Factory integrated type
The protective devices (circuit breakers) are provided for the load lines protection.
The characteristics of those breakers are : 16A – C tripping curves, 6kA short circuit current.
8.3.3
Additional DC filtering – Factory integrated type
Additional DC filtering (additional capacitor or/and chokes) provides low voltage ripple on DC output without battery.
When the battery is connected, the ripple current of the battery is minimized by the additional filter.
1 % filter or 0.1% filter are available.

8.4 BATTERY OPTIONS

8.4.1
Battery output – Factory integrated type
The charger can be equipped with a battery connection branch composed of :
 A battery shunt for battery current measurement.
 A battery end of discharge contactor to protect the battery from deep discharges.
 A battery protection fuse adapted to the charger rating.
 Battery terminals.
Attention : make sure that the battery short circuit current generated by the battery is compatible with the fuse
protection rating and curve.
8.4.2
External battery protection devices – Plug-in type
A battery protection box can be fitted with the equipment. Refer to the option installation manual
BN 09 2671/01/01
- 40 / 50 -