Pressure Sensitive Device Connection; Two-Hand Device Connection - ABB Sentry USR22 Product Manual

Safety relays
Hide thumbs Also See for Sentry USR22:
Table of Contents

Advertisement

Two channels connection with OSSD external signals
7.6

Pressure sensitive device connection

Both T1/R1 and T2/R2 safety inputs must be used for this function. The total resistance of the
circuit including inactivated pressure sensitive devices and cables is shown in chapter.
A force activated pressure sensitive device will result in a short-circuit over T1/R1 and T2/R2. A
short-circuit will inactivate the safety relay output.
T1 and R1 shall be separated in different cables. T2 and R2 shall be separated in different
cables
Pressure sensitive device connection with square wave signals
7.7

Two-hand device connection

A two-hand device has 2 NO and 2 NC contacts. These 4 contacts must be activated within 0.5
seconds in order for the signals to be accepted by the safety relay. If any of the 4 safety device
contacts is inactivated during the process the signal will be unaccepted.
A short-circuit to +24 VDC or 0 V will give an unaccepted signal. All 4 contacts must leave and
return to their unactuated positions before a new accepted signal can be given.