Checking The Usage; Installation - Honeywell Kromschröder GIK Series Operating Instructions Manual

Air/gas ratio control
Table of Contents

Advertisement

2 CHeCKInG tHe UsAGe

Air/gas ratio controls GIK for maintaining a constant
gas/air ratio of 1:1 and for gas pressure control in
systems without preheated combustion air.
Variable air/gas ratio controls GIKH for maintaining
a constant gas/air ratio of 4:1 and for gas pressure
control in systems using a recuperative air preheating
system.
GIK, GIKH for continuous control. GIK..B, GIKH..B
for staged control.
GIK..L, GIKH..L for air only.
This function is only guaranteed when used within the
specified limits  – see page 8 (12 Technical data).
Any other use is considered as non-compliant.
2.1 type code
GIK
15-150
R
F
02
-5
Pressure test point at the outlet
-6
Pressure test point at the inlet and outlet
L
B
With bypass screw (GIK 15-25: 1.5 mm;
ANSI flange version GIK..A available up to DN 100.
GIKH
25
R
02
-5
Pressure test point at the outlet
L
B
2.2 Part designations
GIK..R
5
4
2
Rp 1/4
3
1
1
Adjusting screw
2
Connection for air control pressure
3
Test point for air control pressure
4
Bypass screw
5
Test point for outlet pressure
Air/gas ratio control
Nominal size
Rp internal thread
Flange to ISO 7005
p
max. 200 mbar
u
Only for air (without approval)
GIK 40-50: 5 mm)
Variable air/gas ratio control
Nominal size
Rp internal thread
p
max. 200 mbar
u
Only for air (without approval)
With bypass screw
GIK..F
Rp 1/2
1
3
GIKH
1
Adjusting screw
2
Connection for breather line
3
Bypass screw
4
Connection and test point for air control pres-
sure (+)
5
Connection and test point for air control pres-
sure (–)
6
Test point for outlet pressure
2.3 type label
Technical limits, e.g. max. inlet pressure and control
pressure: see type label or page 8 (12 Technical
data).
Elster GmbH
Osnabrück, Germany
GIK/GIKH

3 InstALLAtIon

CAUtIon
Incorrect installation
Please observe the following to ensure that the
unit is not damaged during installation:
– Always install a manual valve, filter and safety
valve upstream of the air/gas ratio control or
5
variable air/gas ratio control.
– The installation location must be dry, see page
8 (12 Technical data).
– Dropping the device can cause permanent
2
damage. In this event, replace the entire device
and associated modules before use.
– Install the unit in the pipe free of mechanical
stress.
– Do not clamp the unit in a vice or use it as a
lever. Risk of external leakage.
➔ Only install the unit in horizontal pipelines, the spring
dome must point vertically downwards.
➔ We recommend that a slowing down section of
3 x DN be provided downstream of the regulator.
EN-2
6
5
Rp 3/8
4
Rp 3/8
3
2
Rp 1/2
1