SMMS High-Wall Type
5
CUTTING A HOLE AND MOUNTING INSTALLATION
PLATE
Cutting a hole
In case of installing the refrigerant pipes from the
rear:
1. Decide the hole position for piping at
180mm from the arrow mark ( ) on the
installation plate and drill a hole at a slight
downward slant toward outdoor side.
Pipe hole; dia.65mm: AP007-AP018 type
Pipe hole; dia.80mm: AP024 type
80
65
1111012101
The centre of the pipe hole is above the arrow
180mm
NOTE
• When drilling a wall that contains a metal lath,
wire lath or metal plate, be sure to use a pipe
hole brim ring sold separately.
Mounting the installation plate
Be sure that the installation plate is fix to the wall
with screws to make the indoor unit fit to the wall.
Anchor bolt holes
Hook
170
85
Hook
Pipe hole
Thread
Indoor unit
Weight
80
65
1111012101
23mm
Pipe hole
dia. 65mm:
AP007-AP018 type
dia. 80mm:
AP024 type
170
132
23
Pipe hole
Hook
(dia. 65mm
dia. 80mm)
Mounting
Screw
Installation
plate
When the installation plate is
directly mounted on the wall
1. Securely fit the installation plate onto the
wall by screwing it in the upper and lower
parts to hook up the indoor unit.
2. To mount the installation plate on a
concrete wall with anchor bolts, utilize the
anchor bolt holes as illustrated in the above
figure.
3. Install the installation plate horizontally in
the wall.
When installing the installation plate with a
mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
NO
OK
NO
GOOD
GOOD
5mm dia. hole
Clip anchor
(local parts)
Failure to firmly install the unit may result in
personal injury and property damage if the unit
falls.
• In case of block, brick, concrete or similar type
walls, make 5mm dia. holes in the wall.
• Insert clip anchors for appropriate mounting
screws.
NOTE
• Secure four corners and lower parts of the
installation plate with 6 mounting screws to
install it.
36
Installation Manual
CAUTION
Anchor bolt
Projection
15mm or less
Mounting screw
4 × 25
CAUTION

Advertisement