Error Code Table - INVENTOR ATM04S Engineering Data Book

Air conditioning systems, air to water heat pumps - monoblock
Table of Contents

Advertisement

Matrix Mono

12 Error Code Table

Table 3-10.1: Error code table
Error code
C7
Transducer module temperature too high protect
E0
Water flow failure (E8 appears 3 times)
E1
Phase sequence error (for 3 phase models)
E2
Communication error between the main control board of hydraulic module and user interface
E3
Backup electric heater exchanger water outlet temperature sensor T1 error
E4
Domestic hot water tank temperature sensor T5 error
E5
Air side heat exchanger refrigerant outlet temperature sensor T3 error
E6
Outdoor ambient temperature sensor T4 error
E7
Balance tank sensor Tbt1 error
E8
Water flow failure within 3 times
E9
Suction pipe temperature sensor Th error
EA
Discharge pipe temperature sensor Tp error
Eb
Solar board sensor Tsolar error
Ec
Balance tank sensor Tbt2 error
Ed
Water side heat exchanger water inlet temperature sensor Twin error
EE.
Hydronic box EEPROM error
F1
DC generatrix voltage is too low
H0
Communication error between outdoor unit main control chip and hydronic box main control chip
H1
Communication error between outdoor unit main control chip and inverter driver chip
H2
Water side heat exchanger refrigerant outlet (liquid pipe) temperature sensor error
H3
Water side heat exchanger refrigerant inlet (gas pipe) temperature sensor error
H4
Inverter module protection (L0/L1 appear 3 times in one hour)
H5
Room temperature sensor Ta error
H6
DC fan error
H7
Abnormal main circuit voltage
H8
Pressure sensor error
H9
Zone 2 water outlet temperature sensor Tw2 error
HA
Water side heat exchanger water outlet temperature sensor error
PP protection three times in a row and Twout<7℃
Hb
Hd
Communication fault between master unit and slave unit (in parallel)
HE
Communication error between main board and thermostat transfer board
H.F.
Refrigerant system EEPROM error
HH
H6 appears 10 times in 120min
HP
Low pressure protection (pressure < 0.6MPa for 3 times in one hour)
P0
Low pressure protection
P1
High pressure protection
P3
Compressor current protection
P4
Discharge temperature sensor Tp protection
P5
High temperature difference between water side heat exchanger water inlet and water outlet temperatures protection
P6
Inverter module protection
L0
Inverter module protection
L1
DC bus low voltage protection
106