7.

Appendices A

7-1 Dip Switch (at the left side of inverter)
S1
FREQ. (Hz)
ON
60
OFF
50
----
----
----
----
S1 (FREQ. Hz) – 50Hz/60Hz
S2 S3 (BAUD RATE) – 2400 / 4800 / 9600 / 19200
S4 Power Saving Mode – Disable / Enable
When you set up S1~S4, please reset the inverter and let update data through CPU.
7-2 AC Output Voltage Tune (VR)
Tune VR (VAC) output voltage from 100 – 120 VAC or 200 – 240 VAC
The VAC value will gradually increase; tune VR from right to left.
8.

Appendices B

8-1 Power Saving Mode
MICROPROCESSOR BASED SINE WAVE INVERTER SERIES ENABLING AND DILSABLING
POWER SAVING MODE
8-1-1 When an inverter is powered on and is running in idle condition (there is no load or the
load connected to the inverter has been switched off), it will still draw some power from the
batteries for keeping the system alive.
8-1-2 This inverter features a power saving "sleep"mode for conserving the battery power during
idle conditions. When this mode is enabled, the inverter senses the output power being
drawn and if this is less than 2 to 15 watts, the inverter shuts down the output power. Only
essential systems are kept alive to reduce power consumption from the batteries to a very
low value of only about 1.5 watts. As soon as a load is switched on, the inverter wakes up
from its "sleep" condition and restores the output power after a response time of about 8
seconds. Please note that on waking up from the power saving "sleep" mode, the inverter
requires some time to prepare all the systems before it can start delivering power to the
load. Hence, the output power will not be available immediately but after a time lag of
approx. 15 to 18 sec.
If using a hand tool or other appliance with a trigger, keep the trigger pressed for some
time till the power is available to drive the tool / appliance.
RE-MARK:
The user manual is subject to change without notice.
klick to
klick to
www
www
u-s-v
Y O U R C O N N E C T I O N TO S A F E T Y
ACDC-DCDC
S2
S3
BAUD RATE
ON
ON
2400
OFF
ON
4800
ON
OFF
9600
OFF
OFF
19200
klick to
www
Y O U R C O N N E C T I O N TO S A F E T Y
Y O U R C O N N E C T I O N TO S A F E T Y
SYSTEME
S4
POWER SAVING
ON
DISABLE
OFF
ENABLE
----
-----
----
-----
18
klick to
www
Y O U R C O N N E C T I O N TO S A F E T Y
CONTACT
YOUR CONNECTION TO SAFETY
ACV-ADJ
H--------L
240V 200V
H--------L
120V 100V
----
----
klick to
www
Y O U R C O N N E C T I O N TO S A F E T Y
CALLBACK