17.7
Over voltage protection indicator: (OVP)
The over voltage indicator indicates that the power inverter has shut itself down because its input voltage exceed-
ed the maximum input voltage.
17.8
Under voltage protection indicator: (UVP)
The under voltage indicator indicates that the power inverter has shut itself down because its input voltage fell
below minimum input voltage.
17.9
Over temp protection indicator: (OTP)
The over temp indicator indicates that the power inverter has shut itself down because its temp has become over-
heated. The power inverter may overheat because it has been operated at power levels above its rating, or be-
cause it has been installed in a location which does not allow it to dissipate heat properly. The power inverter will
automatically back up, once it has cooled off.
17.10 Overload protection indicator: (OLP)
The overload indicator indicates that the power inverter has shut down. A manual reset is necessary (switch it
OFF and ON again) to restart operation. This is a safety function to protect your battery when the inverter oper-
ates in a remote area.
Model
UPSW2000/3000 12V
UPSW2000/3000 24V
UPSW2000/3000 48V
Manual UPSW.doc
klick to
klick to
www
www
u-s-v
Y O U R C O N N E C T I O N TO S A F E T Y
ACDC-DCDC
DC Input over volt-
DC Input over volt-
age shutdown
age alarm
16.0 VDC
15.5 VDC
32.0 VDC
31.0 VDC
62.0 VDC
61.0 VDC
klick to
www
Y O U R C O N N E C T I O N TO S A F E T Y
Y O U R C O N N E C T I O N TO S A F E T Y
SYSTEME
DC
Input
under
voltage alarm
10.5 VDC
21.0 VDC
43.0 VDC
11/15
klick to
www
Y O U R C O N N E C T I O N TO S A F E T Y
CONTACT
YOUR CONNECTION TO SAFETY
DC
Input
under
voltage shutdown
10.0 VDC
20.0 VDC
42.0 VDC
Version 2.11.14