Summary of Contents for Thiele UPSW2000

  • Page 1 YOUR CONNECTION TO SAFETY Sinewave Inverters 2U 19” Rack-mount Model UPSW2000 and UPSW3000 User’s manual klick to klick to klick to klick to klick to u-s-v Y O U R C O N N E C T I O N TO S A F E T Y...
  • Page 2: Warranty

    YOUR CONNECTION TO SAFETY Warranty RIPEnergy is not manufacturer of these units . All technical information’s, data’s and dimension’s rely on infor- mation’s given by the manufacturer. Therefore RIPEnergy AG is not responsible for the data’s provided in this manual. Should work take place, which is not in accordance with guidelines, local rules, instruction’s or specifica- tion’s, damage may occur.
  • Page 3: Table Of Contents

    YOUR CONNECTION TO SAFETY Contents Warranty..........................2 Distributor’s address......................2 Retail dealer’s address / Date of purchase................2 General Information......................4 Use of this manual....................... 4 Limitation of liability ......................4 Warranty specifications (short form) ..................5 Unpacking..........................5 Environmental protection..................... 5 Description of the inverter....................
  • Page 4: General Information

    YOUR CONNECTION TO SAFETY General Information Thank you for choosing a product supplied by RIPEnergy AG. The product you have bought is manufactured to meet the highest quality standards. Our manufacturers have a very long experience in manufacturing of high end electronic equipment.
  • Page 5: Warranty Specifications (Short Form)

    The inverter is manufactured with valuable materials and easy to recycle. 10 Description of the inverter The model UPSW2000 and UPSW3000 pure sinewave inverter supplies a 230VAC output voltage either from a 12V, 24V or 48VDC power source. The shape of the output voltage is pure sinewave - clean power as from the grid.
  • Page 6: Block Diagram

    YOUR CONNECTION TO SAFETY 11 Block Diagram Version Inverter priority Version Grid priority 12 Safety Information 12.1 General information Read the manual carefully before installing or operating the inverter. If you do not understand or are uncertain about any operation or information please contact your dealer. Before installation you must be aware of local standards and rules applicable to use such equipment.
  • Page 7: Working With Batteries

    YOUR CONNECTION TO SAFETY 12.2 Working with batteries Using batteries in a wrong way may result in danger for personnel, animals or the environment. Check information from battery manufacturer for safe installation and operation. If battery acid contacts skin or clothing, wash immediately with soap and water. If acid contacts eyes, immediately flush with running cold water for at least 20 minutes and get medical attention as soon as possible.
  • Page 8: Ac-Wiring

    YOUR CONNECTION TO SAFETY To thin cable or loose connections can cause dangerous overheating of cables or terminals. Always use DC ca- bles of the correct size to avoid fire and other damage. You may use the following recommendations for best performance of inverter: Inverter DC-Cable AWG / mm2 Inline fuse (A)
  • Page 9: Configure The Inverter Prior To Operation

    YOUR CONNECTION TO SAFETY 15 Configure the inverter prior to operation 15.1 Frequency setting The AC-Frequency may be selected by DIP-Switch S4 on the front panel as follows. AC-Frequency (Hz) To activate the new selected value, the inverter must be turned ON and OFF (Reset) . 15.2 Sleep mode/ Power saving mode (automatic load detection) Power Saving Mode...
  • Page 10: Display

    YOUR CONNECTION TO SAFETY 17 Display Select Key When sequentially push Select Key”, it will display various status on the screen, such as VAC, AMP, WATT… and so on. When malfunction is occurred, its display will be flashed on the screen. 17.1 Output Voltage Indicator LED displays light on VAC as show as output voltage value...
  • Page 11: Over Voltage Protection Indicator: (Ovp)

    DC Input over volt- DC Input over volt- Input under Input under Model age shutdown age alarm voltage alarm voltage shutdown UPSW2000/3000 12V 16.0 VDC 15.5 VDC 10.5 VDC 10.0 VDC UPSW2000/3000 24V 32.0 VDC 31.0 VDC 21.0 VDC 20.0 VDC UPSW2000/3000 48V 62.0 VDC...
  • Page 12: Operating Status

    YOUR CONNECTION TO SAFETY 18 Operating Status 18.1 UPS Mode (OFF line UPS) In this mode, the output of inverter has grid/mains priority. In case of grid/mains failure, the AC-Output switches to inverter power. Switch over time is less than 6ms. If grid/mains power is back within tolerance the load is switched back to grid/mains power.
  • Page 13: Technical Data

    YOUR CONNECTION TO SAFETY 19 Technical data UPSW2000 UPSW3000 Manual UPSW.doc 13/15 Version 2.11.14 klick to klick to klick to klick to klick to u-s-v Y O U R C O N N E C T I O N TO S A F E T Y...
  • Page 14: Trouble Shooting

    YOUR CONNECTION TO SAFETY 20 Trouble shooting Warning – Never remove the cover of the inverter! Do not self repair the inverter, no serviceable parts are inside the unit. Check LED-Display to identify the reason. According the failure indicated by the display see sections below to solve the problem. No function Check wiring for correct size, damage or loose screws.
  • Page 15: Maintenance

    YOUR CONNECTION TO SAFETY 21 Maintenance Only little maintenance is required to keep your inverter and system operating reliable. The inverter must be switched off during maintenance and/or repair activities. It also must be secured against unexpected and uninten- tional switching on. Therefore switch off the connection between batteries and inverter and be sure that third parties cannot reverse the measures taken.