Quantech QCC2015CEE Installation, Operation And Maintenance Manual page 86

Air-cooled scroll compressor condensing units
Table of Contents

Advertisement

SECTION 5 – TECHNICAL DATA
All dimensions in English unless otherwise noted.
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Quantech unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no
higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0''; top –
no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.
86
Dimensions (English)
Dimensions – QCC2015C to 070C (English)
Form QCC2-NM1
Issue Date: 5/20/2021
QUANTECH