Do you have a question about the QCC2015CEE and is the answer not in the manual?
Questions and answers
Summary of Contents for Quantech QCC2015CEE
Page 1
Air-Cooled Scroll Compressor Condensing Units Installation, Operation, and Supersedes: QCC2-NM1 (1220) Form QCC2-NM1 (521) Maintenance 035-26916-000 QCC2015CEE – QCC2070CEE Air-Cooled Scroll Compressor Condensing Units Style E (60 Hz) 15 ton to 80 ton 50 kW to 280 kW R-410A Issue Date:...
Page 2
All wiring must be in accordance with Quantech published specifications and must be performed only by a qualified electri- cian. Quantech will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals.
Page 3
If there is any question this document is subject to change without notice. regarding the applicability of these documents, rig- Quantech makes no commitment to update or provide ging, lifting, and operating/service personnel should current information automatically to the manual or verify whether the equipment has been modified and product owner.
Page 4
Refrigerant level E = R-410a Scroll compressor Across-the- Unit High efficiency unit line start Model 015C Voltage code Quantech Air-Cooled 020C -17 = 208-3-60 Scroll Condensing Units 025C -28 = 230-3-60 030C -40 = 380-3-60 040C -46 = 460-3-60 045C...
Refrigerant Piping Reference ......................... 35 Filter Driers / Sight Glasses/ Txv’s ......................... 35 SECTION 5 – TECHNICAL DATA ........................39 SECTION 6 – COMMISSIONING .........................97 Preparation – Power Off ..........................97 Preparation – Power On ..........................98 Equipment Pre-Startup and Startup Checklist ....................99 QUANTECH...
Page 6
SECTION 10 – MAINTENANCE .........................153 Important ..............................153 Compressors ..............................153 Condenser Fan Motors ..........................153 Condenser Coils ............................153 Operating Parameters ..........................153 On-Board Battery Back-Up ........................... 153 Overall Unit Inspection ..........................153 BACnet, Modbus and YorkTalk 2 Communications ..................154 QUANTECH...
Page 7
Form QCC2-NM1 Issue Date: 5/20/2021 List of figures FIGURE 1 - Quantech Air-Cooled Scroll Compressor Condensing Unit ..............13 FIGURE 2 - Unit Components Front ........................18 FIGURE 3 - Power Panel Components ........................19 FIGURE 4 - Power Panel / Control Components ....................20 FIGURE 5 - Refrigerant Flow Diagram ........................25...
Page 8
TABLE 31 - Minimum, Maximum And Default Values ..................155 TABLE 32 - Values Required For Bas Communication ..................156 TABLE 33 - Real Time Error Numbers .........................156 TABLE 34 - BACnet and Modbus Communications Data Map ................158 TABLE 35 - YorkTalk 2 Communications Data Map .....................163 QUANTECH...
NFPA 70 (National Elec tric Code), ASHRAE/ANSI 15 Safety code for mechanical refrigeration, and are cETL Warranty listed. All units are produced at an ISO 9000-registered Quantech warrants all equipment and materials against facility. defects in workmanship and materials for a period of Compressors...
Air Conditioning Equipment. This manual and any other document supplied with the unit are the property of Quantech which reserves • Conform to Intertek Testing Services, formerly all rights. They may not be reproduced, in whole or in...
Page 11
No the unit. attempt should be made to gain access to the control panel or electrical enclosures during normal operation of the unit. QUANTECH...
Page 12
Form QCC2-NM1 Issue Date: 5/20/2021 THIS PAGE IS INTENTIONALLY LEFT BLANK QUANTECH...
NFPA 70 (National Elec tric Code), ASHRAE/ANSI 15 sure of the coil is 650 psig (45 bar). Safety code for mechanical refrigeration, and are cETL listed. All units are produced at an ISO 9000-registered facility. Figure 1 - Quantech Air-Cooled Scroll Compressor Condensing Unit QUANTECH...
• An RS-232 port, in conjunction with the press-to- • Low ambient temperature cutout setting print button, is provided to allow hard copy print- outs via a separate printer (by others). • English or Metric data • Suction pressure cutout setting • Each system suction pressure QUANTECH...
(load) limiting depending on model. • No cooling load condition • The standard control panel can be directly con- • Day, date and time nected to a Quantech Building Automated Sys- tem. • Daily start/stop times Communications • Holiday status •...
These factory mounted capacitors will correct unit allows models to sense and display discharge pressure. compressor to a power factor between 0.90 and 0.95. This is recommended for brine chilling applications. This option is included with either the low or high am- bient kits. QUANTECH...
Page 17
UV resistance. comparable to copper-fin coils in typical seashore loca- tions. Either these or the post-coated coils (below) are recommended for units being installed at the seashore or where salt spray may hit the unit. QUANTECH...
Level adjusting, spring type 1 in. (25.4 mm) or seismic pitch fans on these factory mounted devices. deflection or neoprene pad isolators for mounting un- der unit base rails. (Field-Mounted) Unit components MICROPANEL FANS COMPRESSORS CONDENSER COILS Figure 2 - Unit Components Front QUANTECH...
Page 22
Hot Gas Bypass Required - 1 Circuit HGBP Hot Gas Bypass (PIN 33) Hot Gas Bypass Required - 2 Circuits Special Hot Gas Bypass Required No Option Required GAUGE PIN 34 Special Quote No Option Required OVERLOAD PIN 35 Special Quote QUANTECH...
Page 23
SR Documents (PIN 50) Base and Material Documents Base and Witness Documents Special Quote No Option Required PIN51 PIN 51 Special Quote Standard Low Sound Fans Required FANS Sound Fans (PIN 52) Ultra Low Sound Fans Required Special Sound Fans Required QUANTECH...
Page 24
Pump Package Options (PIN 60) Special Quote Plant of Mfg (PIN 61) Plant Of Manufacture - Monterrey Curitiba, Brazil Mexico, ES Mfg location Monterrey, BE San Antonio, Texas Yorkworks Configuration Version {YW/CV} YorkWorks version Yorkworks Upload Version {YW/UV} Special quote Special Quote QUANTECH...
Low pressure vapor enters the compres- ing takes place before returning to the DX Coil. sor where pressure and superheat are increased. The QUANTECH...
See Instruction manual, Form 50.15-NM, for more infor- mation and details. Major damage must be reported immediately to your local Quantech Sales Representative. LD14326 Figure 7 - Unit Rigging QUANTECH...
Page 28
The unit must only be lifted by the base frame at the points provided. Never move the unit on rollers, or lift the unit using a forklift truck. QUANTECH...
The units must be installed with sufficient clearances the Quantech Engineering Guide for the specific con- for air entrance to the condenser coil, for air discharge densing unit model. Sound blankets for the compres- away from the condenser, and for servicing access.
No more than 3 feet (1 meter) of light construction ductwork should be supported by the unit. Where cross winds may occur, any ductwork must be supported to prevent side loading on the unit. QUANTECH...
Page 31
33%, 40%, 50%, 66% or 80%, depend- ing on the number of compressors on unit.) The field connections are wired to XTBC1 – Terminals 13 to 21, and work in conjunction with the PWM inputs. A de- QUANTECH...
50. the user. Evaporator blower start contacts QUANTECH ASSUMES NO WARRANTY RE‑ For constant fan operation: Terminal block XTBC2 - SPONSIBILITY FOR SYSTEM OPERATION terminals 23 to 24, are normally open contacts that can...
2.6 ft. (8 m) 7/8 (22) 60.9 92.8 2-1/8 in. (54 mm) 5.2 ft. (1.6 m) 3.4 ft. (1 m) 1-1/8 (29) 60.9 158.3 2-5/8 in. (67 mm) 6.5 ft. (20 m) 4.2 ft. (1.3 m) 1-3/8 (35) 60.9 241.1 QUANTECH...
7/8" for the optional factory mounted hot gas bypass valve. 7. For more information, refer to either the YORK DX Piping Application Guide (Form 050.40-ES2) or the ASHRAE Refrigeration Handbook. Hot gas bypass is only available for refrigerant system number 1. QUANTECH...
The calculat- Liquid line filter driers, sight glass, and TXV’s are ed information was based on maintaining a minimum field supplied for each refrigerant circuit. of 1000 fpm (5.08 m/s) refrigerant vapor velocity at full load. QUANTECH...
NO can result in damage to the evaporator LETHAL VOLTAGES are present inside and unit as a result of the chilled liquid the panel AFTER disconnecting power, freezing. BEFORE working on equipment. Figure 10 - Control Wiring QUANTECH...
Page 38
Form QCC2-NM1 Issue Date: 5/20/2021 THIS PAGE IS INTENTIONALLY LEFT BLANK QUANTECH...
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Quantech Sales Representative for application requirements. 2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest Quantech Sales Representative for application guidelines. 3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
LETHAL VOLTAGES are present inside and unit as a result of the chilled liquid the panel AFTER disconnecting power, freezing. BEFORE working on equipment. Table 8 - Voltage Range VOLTAGE CODE UNIT POWER MINIMUM MAXIMUM 200-3-60 230-3-60 380/415-3-60 460-3-60 380/415-3-50 575-3-60 QUANTECH...
Page 42
FULL LOAD AMPS -50 = 380/415-3-50 HERTZ -58 = 575-3-60 MAXIMUM MINIMUM CIRCUIT AMPACITY MINIMUM MIN NF MINIMUM NON FUSED RATED LOAD AMPS S.P. WIRE SINGLE POINT WIRING UNIT MTD SERV SW UNIT MOUNTED SERVICE (NON-FUSED DISCONNECT SWITCH) LOCKED ROTOR AMPS QUANTECH...
Page 46
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 THIS PAGE IS INTENTIONALLY LEFT BLANK QUANTECH...
Page 47
Pump Contactor Part Wiring And Items Shown Thus Are Not - KP (Including Coil Suppressor) Supplied By York - KT Relay Timer Items Thus Enclosed Form A Compressor Motor Components Or Sets Of Components - MF Motor Fan 035-21966-101 REVG QUANTECH...
Page 48
All sources of supply shown on this diagram to be taken from one main isolator, not shown or supplied by Quantech. Green and yellow wire is used for earth, multi-colored cable used for low voltage. Red wire used for AC Control, blue wire for neutral, black wire for AC and DC power.
Page 49
Fitted on units with single phase motors only Fitted on units with low ambient option only Only fitted on units with an acoustic kit Only fitted on heat recovery units Only fitted on condensing units Omitted on condensing units 035-21966-101 REVG QUANTECH...
Page 50
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 QCC2015C-QCC2030C Low sound QCC2025C-030C Ultra low sound (460 V and 380-415 V 50 Hz) LD22066a Figure 11 - Control Wiring Diagram, Single Circuit, IPU II QUANTECH...
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 035-21472-401 REV E 035-21472-401 REV E LD22066b Figure 11 - Control Wiring Diagram, Single Circuit, Ipu Ii (Cont’d) QUANTECH...
Page 52
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 QCC2025C-030C Ultra low sound (200 V, 230 V, 380 V, and 575 V) LD22067a Figure 12 - Control Wiring Diagram, Single Circuit, IPU II QUANTECH...
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 035-21585-401 REV E LD22067b Figure 12 - Control Wiring Diagram, Single Circuit, IPU II (Cont’d) QUANTECH...
Page 54
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 QCC2040C-QCC2050C Low sound QCC2040C-070C Ultra low sound (460 V and 380-415 V 50 Hz) LD22068a Figure 13 - Control Wiring Diagram, Dual Circuit, IPU II QUANTECH...
6. See installation, operation and maintenance manual when optional equipment is used. 7. Optional current readout. 5 V = 200 A. 8. 1MP through 3MP are contained in their respective compressor junction boxes. Figure 15 - Control Wiring Diagram, Details, Single Circuit QUANTECH...
Page 59
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 035-20964-103 REV D LD22070b Figure 15 - Control Wiring Diagram, Details, Single Circuit (Cont’d) QUANTECH...
6. See installation, operation and maintenance manual when optional equipment is used. 7. Optional current readout. 5 V = 200 A. 8. 1MP through 6MP are contained in their respective compressor junction boxes. Figure 16 - Control Wiring Diagram, Details, Dual Circuit QUANTECH...
Page 61
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 035-20880-103 REV C Figure 16 - Control Wiring Diagram, Details, Dual Circuit (Cont’d) QUANTECH...
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 Power options connection diagrams QCC2015C-QCC2020C Low sound (200 V, 230 V, 380 V, 460 V and 575 V) LD22102a Figure 17 - Power Wiring, Single Circuit QUANTECH...
Page 63
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 035-21487-102 REV B LD22102b Figure 17 - Power Wiring, Single Circuit (Cont’d) QUANTECH...
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 Power options connection diagrams QCC2015C-QCC2020C Low sound (380-415 V/3/50) LD22103a Figure 18 - Power Wiring, Single Circuit QUANTECH...
Page 65
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 035-21487-105 REV B LD22103b figure 18 - Power Wiring, Single Circuit (Cont’d) QUANTECH...
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 QCC2025C-QCC2030C Low sound QCC2025C-QCC2030C Ultra low sound (460 V and 380-415 V/3/50) LD22104a Figure 19 - Power Wiring, Single Circuit QUANTECH...
Page 67
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 035-21472-102 REV D LD22104b FIGURE 19 - Power Wiring, Single Circuit (Cont’d) QUANTECH...
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 QCC2025C-QCC2030C Ultra low sound (200 V, 230 V, 380 V and 575 V) LD22105a Figure 20 - Power Wiring, Single Circuit QUANTECH...
Page 69
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 035-21585-102 REV C LD22105b figure 20 - Power Wiring, Single Circuit (cont’d) QUANTECH...
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 QCC2060C-QCC2070C Low sound QCC2040C-070C Ultra low sound (200 V, 230 V, 380 V and 575 V) LD22113a Figure 28 - Connection Wiring, Dual Circuit QUANTECH...
Page 85
Form QCC2-NM1 SECTION 5 – TECHNICAL DATA Issue Date: 5/20/2021 035-21586-404 REV B LD22113b Figure 28 - Connection Wiring, Dual Circuit (Cont’d) QUANTECH...
Page 86
Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. Quantech unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
(1.3 m) LD13243 NOTES: 1. No obstructions allowed above the unit. 2. Only one adjacent wall may be higher than the unit. 3. Adjacent units should be 10 ft (3 m) apart. Figure 29 - Unit Clearances – All Models QUANTECH...
The selection is made from the local Quantech Sales Rep- drawing will show the isolator locations along with the resentative. Be aware, weights will change with each weight in pounds and kilograms at the specific loca- option along with possible isolator changes.
COLOR CODE CP2-1D-1020 1020 1.020 BLACK CP2-1D-1350 1350 1.320 DK. PURPLE CP2-1D-1800 1800 1.020 DK. GREEN CP2-1D-2400 2400 0.900 GRAY CP2-1D-2720 2720 0.770 WHITE CP2-1D-3570N 3570 0.880 GRAY / RED Figure 32 - One Inch Deflection Spring Isolator Cross-Reference QUANTECH...
(See drawing below). 4. Bolt or anchor all isolators to supporting structure 9. Fine adjust isolators to level equipment. utilizing base slotted holes (“C”). 10. Installation is complete. LD13790 Figure 33 - One Inch Deflection Spring Isolators Installation Instructions QUANTECH...
4. All springs are designed for 50% overload capacity with exception of the 2D-3280N and 2D-2870. 5. Refer to next page for installation instructions. 6. Consult factory for concrete installation. Figure 34 - Two Inch Deflection Seismic Isolator Cross-Reference QUANTECH...
13. Installation is complete. securely to top plate of isolator using a minimum of (2) 5/8 UNC A325 grade 5 SAE bolts or weld equipment or bracket to the top plate (“A”) of LD13763B Figure 35 - Seismic Isolator Installation And Adjustment QUANTECH...
Shim or grout as re- quired, leveling all isolator bases to the same elevation (1/32-in. maximum difference can be tolerated). TOP BOLT ("B") TOP WASHER ("C") ("B") ("A") SECTION D-D LD13762B Figure 37 - Installation of Durulene Vibration Isolators QUANTECH...
Issue Date: 5/20/2021 Section 6 – Commissioning Commissioning of this unit should only Compressor oil be carried out by Quantech Authorized To add oil to a circuit: personnel. 1. Connect a YORK hand oil pump (Part No. 470- 10654-000) to the 1/4 in. oil charging valve with a length of clean hose or copper line, but do not tighten the flare nut.
Verify an air flow switch is correctly fitted in the cus- tomer’s ductwork and wired into the control panel cor- rectly using shielded cable. The air flow switch should be connected to terminals 13 and 14 of XTBC1 on the panel. (See Figure 10 on page 37). QUANTECH...
–refer to Option 2 under “UNIT keys” in sec- minimum capacity............ tion 7 for more information on system switch- 12. Be certain all temp sensors are installed correctly. . es). Connect a manifold gauge to system 1 suction and discharge service valves..... QUANTECH...
Page 100
Fan Differential Off Pressure be temporarily lowered to ensure all com- Total # of Compressors pressors cycle “ON”. Number of Fans/System Unit/Sys Voltage Unit ID Sys 1 Superheat Setpoint Sys 2 Superheat Setpoint * Not on All Models ** Viewable Only QUANTECH...
Introduction Microprocessor board The Microprocessor Board is the controller and deci- The Quantech Millenium MicroComputer Control Center is a microprocessor based control system de- sion maker in the control panel. System inputs such as pressure transducers and temperature sensors are signed to provide the entire control for the liquid con- connected directly to the Microprocessor Board.
It is essential the user become familiar with the use of the keypad and display. This will allow the user to make full use of the capabilities and diagnostic features available. QUANTECH...
Page 105
The REMOTE CONTROLLED SHUTDOWN mes- ready for the lag system to start. sage indicates that either an ISN system or RCC has turned the unit “OFF”, not allowing it to run. QUANTECH...
Page 106
30 minutes. cutout due to high load or pull down conditions. When the unload point is reached, the microboard will auto- matically unload the affected system by de energizing one compressor. The discharge pressure unload will QUANTECH...
Page 107
P R E S S switch opens at 585 psig plus or minus 10 psig (27.92 barg plus or minus .69 barg) and closes at 330 psig plus or minus 25 psig (22.75 barg plus or minus 1.72 barg). QUANTECH...
Page 108
Feedback), this safety will operate as follows. If the actual feedback voltage of the system proportional to Restart will occur after the anti-recycle timer times out. currents exceeds the programmed trip voltage for 5 seconds, the system will shutdown. QUANTECH...
Page 109
PRO- GRAM key is pressed. Once PROGRAM is pressed the anti-recycle timers will be set to the programmed anti-recycle time to allow the operator time to check setpoints, and if necessary, reprogram programmable values and options. QUANTECH...
System X Suction Limiting System X Percentage Load Limiting Manual Overide Status LD13346 System X Pumping Down (on shutdown) * Only displayed when unit control mode programmed for Discharge Air Temperature. ** Only displayed when unit control mode programmed for Suction Pressure. QUANTECH...
Page 111
0.4°F (-17.6°C). The maximum limit on the display is 131.2°F (55.1°C). With the “UNIT TYPE” set as a condensing unit (via jumper between J11-7 and J11-12 on the I/O Board), the following list of operating data screens are view- QUANTECH...
Page 112
30 seconds or if the contacts have been closed in the last 30 seconds. A total of 99,999 hours and starts can be logged before the counter rolls over to “0”. QUANTECH...
Page 113
CURRENT FEEDBACK ONE PER SYSTEM is pro- grammed under the OPTIONS key. Combined com- S Y S L L S V pressor current for each system is displayed. H O T G A S S O L O F F QUANTECH...
Current Feedback One Per System EVAPORATOR PUMP EVAPORATOR HEATER LD13347 ACTIVE REMOTE CONTROL NONE * Block of information repeats for each system UNIT XXX.X AMPS X.X VOLTS SOFTWARE VERSION C.M08.14.02 ** Only displayed when Control Mode is programmed for Discharge Air Temperature Control. QUANTECH...
Page 115
The difference is that the Daily Schedule is not printed in the history print and the header will be as follows. MILLENNIUM CONDENSING UNIT SAFETY SHUTDOWN NUMBER 1 SHUTDOWN @ 3:56PM 29 JULY 09 SYS 1 HIGH DSCH PRESS SHUTDOWN SYS 2 NO FAULTS QUANTECH...
Page 116
S U C T I O N P R E S S U R E Displays the type of Ambient Control; Standard or C U T O U T X X X X P S I G Low Ambient. Displays the programmed Suction Pressure Cutout. QUANTECH...
Page 117
X X X Displays the programmed High Current Trip Voltage. Displays status of the Evaporator Pump and Heater (not installed on a Quantech) at the time of the fault. S Y S 2 T R I P V O L T S X .
Page 118
CURRENT FEEDBACK ONE PER UNIT under the PROGRAM key, the display will be the first dis- play before the SYS 1 info. If the microboard is pro- grammed for CURRENT FEEDBACK NONE, no cur- rent display will appear. QUANTECH...
Page 119
The ↑ (UP) arrow key and ↓ (DOWN) arrow key are also used for programming the control panel such as changing numerical or text values when programming cooling setpoints, setting the daily schedule, changing safety setpoints, unit options, and setting the clock. QUANTECH...
Page 120
ISN control. The message also indicates that I/O Board. the control point is based on Discharge Air Tempera- ture leaving the evaporator. The following are the four possible messages that can be displayed after pressing the COOLING SETPOINT key, indicating the cooling mode: QUANTECH...
Page 121
Suction Pressure Control are the suction pressures just to the desired setpoint, the ENTER/ADV key must of each individual system on the condensing Unit and be pressed to enter this number into memory. will control to within plus or minus the cooling range. QUANTECH...
Page 122
The system can restart when the discharge two part display. The first reads: pressure drops 40 psig (2.76 BARG) below the cutout point. H O L S T A R T 0 0 : 0 0 S T O P 0 0 : 0 0 QUANTECH...
Page 123
If the lead system has run for less than 5 minutes, 3 times in a row, the anti-recycle timer will be extended to 10 minutes maximum. QUANTECH...
Page 124
ID 0-7 is selectable. • Add the sum of the compressor and fan RLA’s in the system • Multiply the sum by 1.25 • Divide by 225 A • The resulting voltage is the value that should be programmed QUANTECH...
ONE PER UNIT Remote Unit Id * The minimum discharge pressure allowed is 160 psig. The fan differential Off Pressure will be lowered to prevent going below 235 psig based on where the fan control On Pressure is programmed. QUANTECH...
(Discharge Air Temp mode only) Fan Control On-Pressure Fan Differential Off-Pressure Total Numbers Compressors Number of Fans Per System YCUL0096 - 0130 ONLY SYS / Unit Trip Volts Option Remote Unit ID SYS 1 & 2 Superheat Setpoints LD08696 QUANTECH...
Page 127
25°F (-3.9°C). This turns system 2 OFF S Y S S W I T C H O F F S Y S S W I T C H QUANTECH...
Page 128
This mode must be chosen if rial units of°F or psig. the discharge pressure transducers are not installed. D I S P L A Y U N I T S This mode displays system operating values in Scien- tific International units of°C or BARG. QUANTECH...
Page 129
This mode should be selected when an optional mod- ule is installed to allow individual current monitoring of each system. SYS 1 input is to J7-4 to J7-12 of the microboard. SYS 2 input is to J9-4 to J9-12 of the mi- croboard. QUANTECH...
Page 130
Temp Reset Input only appears if the Temp Flash Card into the Flash Card input port. Turn off the reset Option is enabled under Service unit switch and set the FLASH CARD UPDATE TO Mode. “ENABLED” using the ↑ and ↓ keys. QUANTECH...
Page 131
O F F minute, meridian; day, month, and year are displayed. Also see the Unit Keys Programming Quick Reference Pressing the ENTER/ADV key will save the valve and List in Table 15. move the cursor on to the next programmable variable. QUANTECH...
Power Failure Restart Soft Start Option Unit Type "Condensing Unit" MUST be Selected Via Jumper Installed (Viewable Only) R410A Refrigerant Type (Programmed Under Service Mode) (Viewable Only LD13348 Table 15 provides a quick reference list for the OPTIONS key setpoints. QUANTECH...
Low Limit, unloading occurs at a rate of 60 sec- onds. The sequences of Capacity Control (compressor staging) for loading and unloading are shown in Table 16 on page 134 and Table 17 on page 134. QUANTECH...
Hot Gas Bypass solenoid is turned OFF when the DAT is more than SP + CR/2. 2. Step 3 is skipped when loading occurs. 3. Step 4 is skipped when unloading occurs. * STEP can be viewed using the OPER DATA key and scrolling to COOLING DEMAND. QUANTECH...
* NOTE: STEP 2 is not active in the “Standard Ambient” mode. When changing to “Low Ambient” control, fan power wiring also changes. Fan #4 Fan #3 Fan #1 LD07403A Fan #2 Figure 40 - QCC2040C – QCC2070C Fan Location (Typical) QUANTECH...
"OAT < 40° F and Stage 2 DP > ctrl_press + 20 DP < ctrl_press - diff_press + 20 TB7-9 3 FWD psig" psig" When Low Ambient Control of the fans is selected, fan control will be by discharge pressure only. QUANTECH...
40% or 33% and is only available on 3, 5 and 6 compressor units. Table 22 on page 139 shows the load limiting permitted for the various numbers of compressors. Simultaneous operation of Remote Load Limiting and EMS-PWM Temperature Reset (described on following pages) cannot occur. QUANTECH...
* Max Reset Value is the “Max EMS-PWM Remote Temp. Reset” set- point value described in the programming section under Cooling Setpoints. Programmable values are from 2°F to 40°F (1.11°C to 11.11°C). **NOTE: The Suction Pressure Setpoints are not remotely resettable. QUANTECH...
ON/OFF or modify the value. Pressing the ↑ (UP) arrow key will energize the liquid line solenoid valve (LLSV) and “OFF” will change to “ON” in the display as the LLSV is energized. Ener- gizing and de-energizing outputs may be useful during troubleshooting. QUANTECH...
(DOWN) arrow keys, but under normal circumstances 2 . 1 V D C P S I G would not be required or advised. After the last start display, the microboard will display the first program- mable value under the PROGRAM key. QUANTECH...
Table 28 - Discharge Air Temp. Sensor Temperature/ J6-6 = +5 VDC regulated supply to sensor. J6-9 = VDC input signal microboard. See Table 28 for voltage readings that correspond to specific outdoor temperatures. J6-3 = drain (shield connection = 0 VDC) Return QUANTECH...
J9-5 = +5 VDC regulated supply to transducer. J9-10 = VDC input signal to the microboard. See the formula above for voltage readings that correspond to specific suction pressures. J7-9 = +5 VDC return. J7-11 = drain (shield connection = 0 VDC). QUANTECH...
Display section. 4. One 25-pin Cannon connector and shell. Connector: Cannon P/N DB-25P or equivalent. Quantech recommends the field tested WEIGH-TRO- Shell: Cannon P/N DB-C2-J9. NIX model 1220 printer (or former IMP 24). This is a compact low cost printer that is ideal for service work Assembly and wiring and data logging.
Page 150
5. Defective IPU II and I/O Board or 5. Replace IPU II and I/O Board or the Display the Display Board. Board. Contact Quantech Service Rep- resentative before replacing circuit Boards! 1. No air flow. 1. Check air flow.
3. Replace defective part. 4. Compressor failure. 4. Diagnose cause of failure and replace. 1. Check DX Coil. 1. Contact the local Quantech representative. 2. Incorrect flow through the DX 2. Reduce flow to within chiller design specs. Coil. See Limitations in Installation section.
Page 152
Form QCC2-NM1 Issue Date: 5/20/2021 THIS PAGE IS INTENTIONALLY LEFT BLANK QUANTECH...
Important Condenser coils If system failure occurs due to incorrect maintenance during the warranty period, Quantech will not be liable Dirt should not be allowed to accumulate on the con- for costs incurred to return the system to satisfactory denser coil surfaces. Cleaning should be as often as operation.
ENGLISH TEXT TOO LONG FLOATING POINT EXCEPTION GET PACKET FAILED GET TYPE FAILED INVALID UNIT CONVERSION INVALID HARDWARE SELECTION REAL TIME FAULT SPANISH TEXT TOO LONG THREAD EXITED THREAD FAILED THREAD STALLED IO BOARD RESET BRAM INVALID BACNET SETUP FAILED QUANTECH...
Page 157
The Modbus Register Address for these points is 1281 + BI #. Refer to Table 33 for complete list of BACnet and Mod- bus registers. The latest data map information is listed on the Quantech Equipment Integration website. QUANTECH...
Table 35 “YorkTalk 2 Communications Data Map” The latest point map information is listed lists the control parameters. These values are found un- on the Quantech Equipment Integration der feature 54 in the MicroGateway or E-Link. website. QUANTECH...
Page 163
Form QCC2-NM1 SECTION 10 – MAINTENANCE Issue Date: 5/20/2021 Table 35 - YorkTalk 2 Communications Data Map QUANTECH...
Need help?
Do you have a question about the QCC2015CEE and is the answer not in the manual?
Questions and answers