SECTION 5 – TECHNICAL DATA
a.
This drawing is based on IEC symbols.
Field wiring to be in accordance with the relevant electrical code as well as all other applicable codes and
b.
specifications.
c.
All sources of supply shown on this diagram to be taken from one main isolator, not shown or supplied by Quantech.
Green and yellow wire is used for earth, multi-colored cable used for low voltage. Red wire used for AC Control, blue
d.
wire for neutral, black wire for AC and DC power. Orange wire should be used for interlock control wiring supplied by
external source.
Legend designation depicts component abbreviations. Number prefix located, if applicable, on schematic circuit, refers
e.
to system thereon, E.G. = 1-FHP2 refers to high pressure cutout no 2 on system no 1.
f.
YLAA
g.
Customer voltage free contacts connected to terminal 13 must be rated at 30V 5ma.
No controls {relays etc.} Should be mounted in any section of the control panel. Additionally, control wiring not
h.
connected to the YORK control panel should not be run through the panel. If these precautions are not followed,
electrical noise could cause malfunctions or damage to the unit and its controls.
I
120/14.3 -(Signal Input) i.e. 120 is wire # and 14.3 refers to sht. 14 column 3
Refer to installation commissioning operation and maintenance manual for customer connections and customer
1
connection notes, non compliance to these instructions will invalidate unit warranty.
Wiring and components for compressor 3 only fitted when unit has 3 compressors on the system. 1-BMP3 is replaced
2
by a link across terminals 134 and 135. 2-BMP3 is replaced by a link across terminals 234 and 235.
3
4
Fitted on units with hot gas bypass option.
5
EMS option is wired as shown.
6
This wiring must be used for old display 031-0110-000.
7
Network connection point.
8
Printer port.
9
Remote emergency stop can be wired between terminal l and 5 after removing link.
10
Power factor correction accessory. Power factor correction fitted to each compressor contactor.
Not fitted on compressors with internal motor protection. For system 1 terminals 132 and 133, 133 and 134 and 134
11
and 135 are linked. For system 2 terminals 232 and 233, 233 and 234 and 234 and 235 are linked.
12
Only fitted on systems with 3 or 4 fans.
13
Only fitted on systems with 4 fans.
14
Only fitted on systems with 5 fans.
15
Only fitted on systems with 6 fans.
16
Input switch disconnect (standard on CE units) or circuit breaker option replaces input terminal block.
17
Input switch disconnect and individual system circuit breaker option replaces input terminal block.
115V control circuit requires a 115V supply unless control circuit transformer -T2 and -F3 are fitted (standard on CE
18
units).
For optional hydro kit. Heater -EPH is fitted and wired as shown. On single pump -KP1, -QMMSP1 and -MP1 are fitted
19
and wired as shown. On two pump hydro kits -KP2, -QMMSP2 and -MP2 are also fitted and wired as shown.
20
Current measurement option wired as show.
21
Only fitted on systems with single speed fans.
22
Only fitted on systems with two speed fans.
23
Optional compressor manual motors starters (standard on CE units).
24
See sheet 3 of connection diagram for power input options.
25
Alternate connections shown for different two speed motor types.
48
Electrical notes and legend (cont'd)
GENERAL
NOTES
Form QCC2-NM1
Issue Date: 5/20/2021
035-21966-101 REVG