Mitsubishi Electric MSZ-LN18VGW - E1 Service Manual page 33

Split-type air conditioners
Table of Contents

Advertisement

D How to check miswiring and serial signal error
MUZ Type
Check for incorrect indoor-outdoor connecting wiring.
Yes
The connection information to the Multi series is stored
in the indoor unit. Refer to "Deleting the memorized
abnormal condition" described in 10-2.1 to clear the error
history. When the error history is being cleared, the con-
nection information also will be initialized. The indoor unit
will be compatible with a low-standby-power model after
initialization.
OK
Is there rated voltage between outdoor terminal block S1 and S2?
Wait for 2 or more minutes after the power supply is turned on.
Touch S2 and S3 with tester probes and start the emergency operation.
When the emergency operation starts, does the rated voltage occur for 2
seconds between indoor terminal block S2 and S3?
Yes
Does the indoor POWER lamp
blink continuously 6 minutes after
the emergency operation starts?
Yes
Does the outdoor LED blink 6
times?
Yes
Does DC (6 V or more) occur
between indoor terminal block S2
and S3?
Yes
Turn the power supply OFF.
Replace the indoor power P.C.
board.
Turn the power supply ON.
Start the emergency operation.
Does the indoor POWER lamp
blink continuously 6 minutes after
the emergency operation starts?
Yes
Does DC (20 V or more) occur
between indoor terminal block S2
and S3?
Yes
Replace the indoor electronic
control P.C. board.
OBH766B
Turn OFF the power supply.
Is there rated voltage in the power supply?
Yes
Was the indoor unit ever connected to
the Multi (MXZ) series and operated
(turned on)?
A
B
Turn the power supply ON.
Yes
No
Does the outdoor LED light up?
Yes
Confi rm that the thermostat is OFF
and wiring is not loose.
No
Replace the outdoor inverter P.C. board.
No
Replace the outdoor inverter P.C. board.
Electric charge may remain immediately
*1
after the power supply is turned OFF.
Perform the procedure after 3 minutes.
No
Repair completed.
No
Replace the outdoor inverter P.C. board.*1
Check the power supply.
No
No
Check for miswiring, broken wires, and loose
No
wire connection between the power supply and
outdoor terminal block S1 and between the
power supply and outdoor terminal block S2.
No
MUZ-LN25/35/50
Turn the power supply OFF.
No
Turn the power supply ON.
Wait for 2 or more minutes after the
power supply is turned ON. Touch
CN202
and GND with tester probes
and start the emergency operation.
*1
During the emergency opera-
tion, does DC (2V or less) occur
*1
for 2 seconds between CN202
and GND on the indoor elec-
tronic control P.C. board?
Replace the
indoor power P.C.
board.
• Turn OFF inverter-controlled lighting
equipment.
• Turn OFF the power supply and then
turn ON again.
• Press EMERGENCY OPERATION
switch.
Is serial signal
error indicated 6
minutes later?
B
33
MUZ-LN60
Replace the indoor
electronic control
P.C. board.
No
Yes
Replace the indoor
electronic control
P.C. board.
A
• Reinstall
either the unit
or the light
away from
each other.
• Attach a fi lter
No
on remote
control receiv-
Yes
ing section
of the indoor
unit.