Goodman Amana AMH8 Service Instructions Manual page 22

33 3/8" 80% modified two stage gas furnaces
Hide thumbs Also See for Amana AMH8:
Table of Contents

Advertisement

PRODUCT DESIGN
Thermostat Location
In an area having good air circulation, locate the ther-
mostat and dehumidistat (if applicable) about five feet
high on a vibration-free inside wall. Do not install the
thermostat or dehumidistat where it may be influenced
by any of the following:
Drafts, or dead spots behind doors, in corners, or
under cabinets.
Hot or cold air from registers.
Radiant heat from the sun.
Light fixtures or other appliances.
Radiant heat from a fireplace.
Concealed hot or cold water pipes, or chimneys.
Unconditioned areas behind the thermostat and
dehumidistat, such as an outside wall.
Consult the instructions packaged with the thermostat
and dehumidistat for mounting instructions and further
precautions.
COMBUSTION AND VENTILATION AIR
REQUIREMENTS
P
OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH MAY OCCUR
IF THE FURNACE IS NOT PROVIDED WITH ENOUGH FRESH AIR FOR PROPER
COMBUSTION AND VENTILATION OF FLUE GASES. MOST HOMES REQUIRE
OUTSIDE AIR BE SUPPLIED TO THE FURNACE AREA.
Improved construction and additional insulation in build-
ings have reduced heat loss by reducing air infiltration
and escape around doors and windows. These changes
have helped in reducing heating/cooling costs but have
created a problem supplying combustion and ventilation
air for gas fired and other fuel burning appliances. Ap-
pliances that pull air out of the house (clothes dryers,
exhaust fans, fireplaces, etc.) increase the problem by
starving appliances for air.
If this furnace is to be installed in the same space with
other gas appliances, such as a water heater, ensure
there is an adequate supply of combustion and ventila-
tion air for the other appliances. Refer to the latest
edition of the National Fuel Gas Code NFPA 54/ANSI
Z223.1 (Section 9.3), or CAN/CGA B149 Installation Codes
(Sections 7.2, 7.3, or 7.4), or applicable provisions of
the local building codes for determining the combustion
air requirements for the appliances.
Most homes will require outside air be supplied to the
furnace area by means of ventilation grilles or ducts
connecting directly to the outdoors or spaces open to
the outdoors such as attics or crawl spaces.
The following information on air for combustion and ventila-
tion is reproduced from the National Fuel Gas Code NFPA
54/ANSI Z223.1 Section 9.3.
22
WARNING
9.3* Air for Combustion and Ventilation.
9.3.1 General.
9.3.1.1 Air for combustion, ventilation, and dilution of flue gases for
appliances installed in buildings shall be obtained by application of one of
the methods covered in 9.3.2 through 9.3.6. Where the requirements of
9.3.2 are not met, outdoor air shall be introduced in accordance with methods
covered in 9.3.3 through 9.3.6.
Exception No. 1: This provision shall not apply to direct vent appli-
ances.
9.3.1.2 Appliances of other than natural draft design and other than Cat-
egory 1 vented appliances shall be provided with combustion, ventilation,
and dilution air in accordance with the appliance manufacturer's instruc-
tions.
9.3.1.3 Appliances shall be located so as not to interfere with proper
circulation of combustion, ventilation, and dilution air.
9.3.1.4 Where used, a draft hood or a barometric draft regulator shall be
installed in the same room or enclosure as the appliance served so as to
prevent any difference in pressure between the hood or regulator and the
combustion air supply.
9.3.1.5 Makeup air requirements for the operation of exhaust fans, kitchen
ventilation systems, clothes dryers, and fireplaces shall be considered in
determining the adequacy of a space to provide combustion air require-
ments.
9.3.2 Indoor Combustion Air. The required volume of indoor air shall
be determined in accordance with the method in 9.3.2.1 or 9.3.2.2 except
that where the air infiltration rate is known to be less than 0.40 ACH, the
method in 9.3.2.2 shall be used. The total required volume shall be the
sum of the required volume calculated for all appliances located within the
space. Rooms communicating directly with the space in which the appli-
ances are installed through openings not furnished with doors, and through
combustion air openings sized and located in accordance with 9.3.2.3, are
considered a part of the required volume.
9.3.2.1* Standard Method. The minimum required volume shall be 50
ft
3
per 1,000/Btu/hour (4.8m
3
9.3.2.2* Known Air Infiltration Rate Method. Where the air infiltra-
tion rate of a structure is known, the minimum required volume shall be
determined as follows:
(1) For appliances other than fan-assisted, calculate using the following
equation:
Required Volume
other
(2) For fan-assisted appliances, calculate using the following equation:
Required Volume
> ________ _________
fan
where:
I
=
all appliances other than fan-assisted input in Btu per hour
other
I
=
fan-assisted appliances input in Btu per hour
fan
ACH
=
air change per hour (percent of volume of space exchanged
per hour, expressed as a decimal)
/kW).
(
)
21 ft
3
I
> ________ _________
other
ACH
1000 Btu/hr
(
)
15 ft
3
I
fan
ACH
1000 Btu/hr

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Amana gmh8Amana gdh8Amana adsh8

Table of Contents