Daikin D2CND024A4AB Installation Manual page 23

Wall-mounted condensing boiler
Hide thumbs Also See for D2CND024A4AB:
Table of Contents

Advertisement

a
b
c
b
d
e
f
a
Flex kit PP Dn 60-80 or Dn 80
b
Spacer
c
Extension Flex PP 80 mm
d
Connector Flex-Flex PP 80 mm
e
Chimney connection 60/100 or 80/125
f
90° elbow 60/100 (boiler outlet)
Optional:
g
Inspection elbow 60/100
h
30° elbow 60/100
i
45° elbow 60/100
j
Extension 80/125
L = 500-1000 mm
Instead of 60/100, 80/125 flue ducts can be used at the outlet of the
boiler. In that case, the parts below are used:
a
b
c
a
60/100 to 80/125 adapter
b
90° elbow 80/125
c
45° elbow 80/125
d
30° elbow 80/125
e
Extension 80/125
L = 500-1000 mm
Allowable flue length for C93x (for D2C* )
Shaft
60-100
circular and smooth
Concentric
DN 60 Flex
circular and rough
DN 60 Flex
circular and rough
DN 60 Flex
square and rough
DN 60 Flex
square and rough
80-125
circular and smooth
Concentric
DN 80 Flex
circular and rough
DN 80 Flex
circular and rough
D2CND024A1/4AB + D2TND012~024A4AB
Wall-mounted condensing boiler
3P469346-3N – 2019.11
g
h
i
j
L
d
e
Chimney
Parameter
cross-
C3
section
"3"
"5"
100
9.0
15.0
106
4.2
7.0
100
3.0
5.0
95
4.2
7.1
90
3.2
5.3
124
28.0
99.0
140
15.0
52.9
130
9.6
33.8
Allowable flue length for C93x (for D2C* )
DN 80 Flex
circular and rough
DN 80 Flex
square and rough
DN 80 Flex
square and rough
DN 80 Flex
square and rough
DN 80 Star
square and rough
DN 80 Star
square and rough
Allowable flue length for C93x (for D2T/H* )
Chimney cross-section PP 60 mm rigid duct
Circular Ø100 mm
Circular Ø120 mm
Circular Ø140 mm
Square 100×100 mm
Square 120×120 mm
Square 140×140 mm
10.0 m
Chimney cross-section PP 80 mm rigid duct
Circular Ø120 mm
Circular Ø140 mm
15.4 m
Circular Ø160 mm
18.6 m
Square 120×120 mm
Square 140×140 mm
15.4 m
Square 160×160 mm
18.6 m
Equivalent length of options
45° elbow 60/100 mm
90° elbow 60/100 mm
45° elbow 80/125 mm
90° elbow 80/125 mm
Maximum allowable length of the flue duct up to common
chimney is 2 metres + 1 60/100 90° elbow.
Subtract equivalent length value of bends from the allowable flue
length value.
Type B53 (open flue system)
WARNING
Make sure that an air inlet opening to outside of at least
150 cm² is provided.
The boiler draws combustion air from the installation room and
expels flue gas through the flue to above the roof (1).
The boiler draws combustion air from the installation room and
routes flue gas through the moisture-resistant chimney to above the
roof (2).
Allowable flue length for B53
4 Installation
120
3.6
12.8
140
19.6
69.2
130
17.0
60.0
120
12.2
43.0
140
47.5 167.8
120
33.3 117.9
PP 60 mm flexible
duct
7.2 m
2.9 m
9.3 m
4.5 m
9.9 m
4.8 m
8.8 m
5.1 m
9.7 m
6.1 m
6.2 m
PP 80 mm flexible
duct
5.0 m
5.0 m
15.4 m
18.6 m
5.0 m
13.3 m
18.3 m
19.4 m
1.0 m
1.5 m
1.0 m
1.5 m
D2T/H*
D2C*
Installation manual
23