Symptom: Noise of air conditioners
(Indoor unit)
▪ A "zeen" sound is heard immediately after the power supply is
turned on. The electronic expansion valve inside an indoor unit
starts working and makes the noise. Its volume will reduce in
about one minute.
▪ A continuous low "shah" sound is heard when the system is in
cooling operation or at a stop. When the drain pump (optional
accessories) is in operation, this noise is heard.
▪ A "pishi-pishi" squeaking sound is heard when the system stops
after heating operation. Expansion and contraction of plastic parts
caused by temperature change make this noise.
▪ A low "sah", "choro-choro" sound is heard while the indoor unit is
stopped. When another indoor unit is in operation, this noise is
heard. In order to prevent oil and refrigerant from remaining in the
system, a small amount of refrigerant is kept flowing.
8.2.10
Symptom: Noise of air conditioners
(Indoor unit, outdoor unit)
▪ A continuous low hissing sound is heard when the system is in
cooling or defrost operation. This is the sound of refrigerant gas
flowing through both indoor and outdoor units.
▪ A hissing sound which is heard at the start or immediately after
stopping operation or defrost operation. This is the noise of
refrigerant caused by flow stop or flow change.
8.2.11
Symptom: Noise of air conditioners
(Outdoor unit)
When the tone of operating noise changes. This noise is caused by
the change of frequency.
8.2.12
Symptom: Dust comes out of the unit
When the unit is used for the first time in a long time. This is
because dust has gotten into the unit.
8.2.13
Symptom: The units can give off odours
The unit can absorb the smell of rooms, furniture, cigarettes, etc.,
and then emit it again.
8.2.14
Symptom: The outdoor unit fan does not
spin
During operation. The speed of the fan is controlled in order to
optimise product operation.
For the installer
11
About the box
11.1
About
is part of Daikin's wider commitment to reduce our
environmental footprint. With
economy for refrigerants. One of the actions to achieve this, is the
reuse of reclaimed refrigerant in VRV units produced and sold in
Europe. For more information about the countries that are in scope,
visit: http://www.daikin.eu/loop-by-daikin.
Installation and operation manual
12
we want to create a circular
8.2.15
Symptom: The display shows "88"
This is the case immediately after the main power supply switch is
turned on and means that the user interface is in normal condition.
This continues for 1 minute.
8.2.16
Symptom: The compressor in the outdoor
unit does not stop after a short heating
operation
This is to prevent refrigerant from remaining in the compressor. The
unit will stop after 5 to 10 minutes.
8.2.17
Symptom: The inside of an outdoor unit is
warm even when the unit has stopped
This is because the crankcase heater is warming the compressor so
that the compressor can start smoothly.
8.2.18
Symptom: Hot air can be felt when the
indoor unit is stopped
Several different indoor units are being run on the same system.
When another unit is running, some refrigerant will still flow through
the unit.
9
Relocation
Contact your dealer for removing and reinstalling the total unit.
Moving units requires technical expertise.
10
Disposal
This unit uses hydrofluorocarbon. Contact your dealer when
discarding this unit.
NOTICE
Do NOT try to dismantle the system yourself: dismantling
of the system, treatment of the refrigerant, oil and other
parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for
reuse, recycling and recovery.
11.2
To remove the accessories from
the outdoor unit
Make sure that all accessories are available in the unit.
a
b
c
REQUEST FOR THE INDICATION OF INSTALLATION INFORMATION
BE SURE TO FILL OUT THE BLANKS, WHICH ARE NEEDED FOR AFTER-SALE SERVICES.
1. RECORD OF INDOOR UNIT MODEL AND INSTALLATION SITE
No.
1
2
3
4
5
6
7
8
MODELNAME
INSTALLATION
SITE
No.
11
12
13
14
15
16
17
18
MODELNAME
INSTALLATION
No.
SITE
21
22
23
24
25
26
27
28
MODELNAME
INSTALLATION
SITE
No.
31
32
33
34
35
36
37
38
MODELNAME
INSTALLATION
No.
SITE
41
42
43
44
45
46
47
48
MODELNAME
INSTALLATION
No.
SITE
51
52
53
54
55
56
57
58
MODELNAME
INSTALLATION
SITE
No.
61
62
63
64
MODELNAME
INSTALLATION
SITE
2. RECORD FOR SETTINGS (CONTENTS SEE INSTALLATION MANUAL)
SETTING
VALUE
REMARK
DATE
SETTING
VALUE
REMARK
3. RECORD OF INSTALLATION DATE
DAY
MONTH
YEAR
4. MODEL NAME
5. MANUFACTURING NUMBER
6. AFTER EQUIPPING, PLEASE PUT IT ON THE BACK SIDE OF THE FRONT PLATE.
a
General safety precautions
b
Installation manual and operation manual
c
Additional refrigerant charge label
d
Installation information sticker
VRV IV+ heat pump for high ambient temperatures
d
e
REQUEST FOR THE INDICATION OF ADDITIONAL REFRIGERANT CHARGING AND LEAK DETECTION OPERATION RESULT
BE SURE TO FILL OUT THE BLANKS, WHICH ARE NEEDED FOR AFTER-SALE SERVICES.
9
10
1. CALCULATION OF ADDITIONAL REFRIGERANT CHARGING AMOUNT
CALCULATE THE ADDITIONAL REFRIGERANT CHARGING AMOUNT BASED ON THE FORMULA BELOW BEFORE CHARGING.
SHIPMENT (INDICATED ON THE MACHINE NAMEPLATE) AND THE ADDITIONAL AMOUNT SHOWN AS FOLLOWS :
WHEN RE-CHARGING TOTAL AMOUNT OF REFRIGERANT , CHARGE THE TOTAL OF THE AMOUNT CHARGED AT
19
20
Total indoor unit
capacity connection
Total indoor unit capacity
kg
ratio (CR)
50%< CR < 105%
0
8HP
10-12HP 14-16HP 18-20HP
0
0
0.5
OUTDOOR
ADDITIONAL CHARGING
TOTAL LENGTH OF LIQUID
TOTAL LENGTH OF LIQUID
TOTAL LENGTH OF LIQUID
when piping length <30m
105%< CR < 130%
0.5
0.5
0.5
1.0
29
30
UNIT
AMOUNT
kg
PIPE SIZE O22.2 x 0.37
PIPE SIZE O19.1 x 0.26
PIPE SIZE O15.9 x 0.18
Total indoor unit capacity
70%< CR < 85%
50%< CR < 70%
0.3
0
0
0.5
0.5
0
1.0
0.5
(m) x 0.37
(m) x 0.26
(m) x 0.18
when piping length >30m
105%< CR < 130%
85%< CR < 105%
1.2
0.7
1.5
1
1
1.5
2.0
1.5
TOTAL LENGTH OF LIQUID
PIPE SIZE O12.7 x 0.12
PIPE SIZE O9.5 x 0.059
TOTAL LENGTH OF LIQUID
PIPE SIZE O6.4 x 0.022
TOTAL LENGTH OF LIQUID
39
40
(m) x 0.022
ONLY FOR RYYQ8~20 MODELS
RYYQ8~12
RYYQ14-16
RYYQ18-20
(m) x 0.12
(m) x 0.059
kg
0.9
1.1
1.3
2. RECORD OF ADDITIONAL REFRIGERANT CHARGE AMOUNT AND RESULT OF LEAK CHECK OPERATION
49
50
DATE
AMOUNT
59
60
RESULT LEAK CHECK
DATE
AMOUNT
RESULT LEAK CHECK
DATE
AMOUNT
DATE
RESULT LEAK CHECK
DATE
AMOUNT
RESULT LEAK CHECK
3. FOR DETAILS CONCERNING PIPING SELECTION AND CALCULATION OR HOW TO OPERATE THE LEAK DETECTION FUNCTION, PLEASE REFER TO THE INSTALLATION MANUAL.
4. AFTER FILLING IN THIS TABLE, PLEASE PUT IT ON THE SWITCH BOX COVER.
3P328191-1
3P328192-1
RXYTQ8~16U7YF
4P546223-1B – 2020.10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxytq8u7yfRxytq10u7yfRxytq12u7yfRxytq14u7yfRxytq16u7yf

Table of Contents