Connect the terminals on top of the front part of the digital
controller and the terminals inside the unit (P1 to 16, P2 to 16a).
NOTICE
When wiring, run the wiring away from the power
supply wiring in order to avoid receiving electric
noise (external noise).
Peel the shield for the part that
has to pass through the inside of
the digital controller case ( l ).
4
Reattach the upper part of the digital controller.
CAUTION
Be careful not to pinch the wiring when attaching.
First begin fitting from the clips at the
bottom.
8.
S
-
TART
UP AND CONFIGURATION
The indoor unit should be configured by the installer to match the
installation environment (outdoor climate, installed options, etc.) and
user expertise.
CAUTION
It is important that all information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.
DANGER: ELECTRIC SHOCK
See
"2. General safety precautions" on page

8.1. DIP switch settings overview

DIP switch SS2 is located on the switch box PCB (see
box main components" on page
domestic hot water tank installation, room thermostat connection and
pump operation.
WARNING
Switch off the power supply before opening the switch box
service panel and making any changes to the DIP switch
settings.
Installation manual
23
2.
"5.3. Switch
11) and allows configuration of
1
2
3
4
DIP
switch
SS2
Description
1
Not applicable for installer
2
Domestic hot water tank
installation
(see
"8.4. Domestic hot
water tank installation
configuration" on page
3
Room thermostat
connection
(see
"8.2. Room
thermostat installation
configuration" on page
4
This setting
operation mode of the
heat pump when there is a
simultaneous demand for
more space heating/
cooling and domestic
water heating.
(a) Only applicable in case DIP switch 2 = ON.
(b) Heating/cooling or domestic water heating mode can be restricted by schedule
timer and/or field settings (4, 5, 8).
8.2. Room thermostat installation configuration
1
When no room thermostat is connected to
the indoor unit, toggle switch SS2-3 should be
set to OFF.
When the room thermostat is connected to
the indoor unit, toggle switch SS2-3 should be
set to ON.
On the room thermostat, confirm the correct settings (6®02=yes,
6®05=9, 6®06=5) to prevent the pump from repeatedly turning on
and off (i.e. chattering), and thereby impacting the lifetime of
the pump.
INFORMATION
When the room thermostat is connected to the indoor
unit, the heating and cooling schedule timers are
never available. Other schedule timers are not
affected. For more information on the schedule timers,
refer to the operation manual.
When the room thermostat is connected to the indoor
unit, and the = button or y button is pressed, the
centralised control indicator e will flash to indicate
that the room thermostat has priority and controls on/
off operation and change over operation.
The following table summarizes the required configuration and
thermostat wiring at the terminal block (X2M: 1, 2, 3, 4) in the switch
box. Pump operation is listed in the third column. The three last
columns indicate whether the following functionality is available on
the user interface (UI) or handled by the thermostat (T):
space heating or cooling on/off (y)
heating/cooling changeover (=)
heating and cooling schedule timers (pr)
ON
Installed
24)
Room thermostat
connected
23)
(a)
decides the
Heating/cooling
priority
Indoor unit for air to water heat pump system
OFF
(Default)
Not installed
(Default)
No room
thermostat
connected
(Default)
Priority to highest
(b)
demand side
1
2
3
4
1
2
3
4
EKHBH/X016BB
4PW62572-1A – 01.2011