UTICA BOILERS SSC UBSSC-075 Installation Operation & Maintenance page 38

Wall mounted gas boiler
Table of Contents

Advertisement

9.4 Boiler Start-up and Operational Test
1.
Verify air is purged from hydronic piping
2.
System test pumps - verify each pump is
operational
3.
Verify gas piping
• Confi rm pressure test. See section 7.3.
• Visually inspect piping to determine there are no
open fi ttings or ends, and all valves at unused
outlets are closed and plugged/capped.
• Purge air from piping
• Check piping and connections for leaks
immediately after gas is turned on. Shut off
gas supply and make necessary repairs if leaks
found.
4.
Follow OPERATING INSTRUCTIONS to initiate boiler
operation. See section 10.
5.
Inspect combustion air and vent piping. Verify pipe
is not leaking and terminations are unobstructed
and vent gas discharge is not a nuisance or hazard.
6.
Verify boiler functions.
7.
Inspect condensate disposal system. Verify
condensate fl ows adequately and is disposed
properly.
8.
Check control module operation.
9.
Check fi eld sourced limits, low water cutoffs, etc.
per manufacturer's instructions.
9 - START UP PROCEDURE
9.5 Check Combustion
Natural Gas
1.
Measure input. English units*
• Turn off gas to all other appliances.
• Activate some heating zones to dissipate heat.
• Set boiler on high fi re.
• Use ½, 1 or 2 cu ft dial on gas meter. Measure
• Calculate input.
Input (MBH)
Example: Gas fl ow from
Rate (MBH)
*Metric - See Glossary
2.
Compare measured input to table. Adjust input rate
if needed using Table 12 below.
Table 12 - Rate @ High Fire
Natural Gas and Propane
3.
Measure CO
Adjust CO
fi gures 9-5 and 9-6 for combustion air analyzer
port.
38
time required for one or more complete
revolutions. Measure time for 1-2 minutes.
3600 x
=
Meter = 2 cu ft
Measured time = 72 seconds
3600 x 2 cu ft
=
72 seconds
Rate @ High Fire
Size
From
050
45
075
65
100
90
150
140
200
185
299
285
at high fi re and compare to table.
2
if needed using fi gure 9-3 & 9-4. See
2
cu ft
seconds
=
100 MBH
To
51
76
102
153
204
315

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents