Evacuating The Indoor Unit; Cutting Or Extending The Pipe - Samsung AR-KP/JP Series User & Installation Manual

Table of Contents

Advertisement

Evacuating the indoor unit

The indoor unit is supplied with inert gas (nitrogen).
Before installing the unit, check if nitrogen gas flow out of indoor unit.
If this one isn't true, DO NOT INSTALL THE UNIT since leakage could be inside the indoor unit.
1. Unscrew the caps at the end of each pipe.
All inert gas exhausts from the indoor unit.
• T o prevent dirt or foreign substances from getting into the
pipes during installation, do NOT remove the caps completely
until you are ready to connect the pipes.
• T he remaining air in the Refrigeration cycle, which contains
moisture, may cause malfunction on the compressor.
• A lways contact the service center or a professional installation
agency for product installation.

Cutting or extending the pipe

The length of the pipe can be:
• Extended up to : see table page 31
• Shorten up to: see page 31
If you need a pipe longer than 7.5 meters:
• You must add refrigerant to the pipes; otherwise, the indoor unit may freeze.
1. Make sure that you have all the required tools (pipe cutter, reamer, flaring tool and pipe holder).
2. If you want to shorten the pipe, cut it using a pipe cutter, ensuring that the cut edge remains at 90° with the side of the
pipe (see below examples of correct and incorrect cut edges).
Pipe
cutter
Pipe
3. To prevent a gas leak, remove all burrs at the cut edge of the pipe using a reamer.
• Face the pipe down while removing the burrs to make sure that burrs do not get in to the pipe.
Oblique
Rough
English-40
Pipes
Burr
Unscrew the caps

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ar-kc/jc seriesAs32u seriesAr30kcfuduq/qt

Table of Contents