Choosing the installation location
Space Requirements for Outdoor Unit
When installing 1 outdoor unit
 Figure Description
Top view
Air intake
Air outlet
,
Air flow direction
 When the air outlet is opposite the
wall
 The upper part of the outdoor unit
and the air outlet is towards the wall
2000 or more
When installing more than 1 outdoor unit
 When the air outlet is towards the wall
Air outlet
.
 When the air outlet is towards the
wall
 The upper part of the outdoor unit
and the air outlet is opposite the
wall
Side view
Air intake
300 or more
 When 3 sides of the outdoor unit are blocked by the wall
300 or more
600 or more
English-32
 When 3 sides of the outdoor unit are
blocked by the wall
150 or more
600 or more
 When the walls are blocking front
and the rear side of the outdoor unit
600 or more
600 or more
(Unit : mm)
(Unit : mm)