Carrier Smartvu Control Manual page 24

For 50/48 uc-(v)/up-(v) 025-220
Hide thumbs Also See for Smartvu:
Table of Contents

Advertisement

5 - SMARTVU CONTROL: MENU STRUCTURE
Setpoint – SETPOINT
Point Name
blank
occ_cool
uno_cool
occ_heat
uno_heat
frst_sp
blank
oc_rh_sp
oc_rh_db
un_rh_sp
un_rh_db
blank
purg_low
purg_hig
purg_du
iaq_sp
Trendings – TRENDING
Name
GENUNIT_cap_t
GENUNIT_CTRL_PN
TEMP_OAT
TEMP_SAT
TEMP_SPT
TEMP_SCT_A
TEMP_SCT_B
TEMP_SST_A
TEMP_SST_B
*Depends on the selected language (English by default).
**The list of trending points cannot be modified. Trending points can only be enabled or disabled.
22
Status
Default
50 to 89.6
78.8
50 to 89.6
82.4
50 to 75.2
66.2
50 to 75.2
62.6
50 to 75.2
59
10 to 80
50
10 to 50
10
10 to 80
70
10 to 50
30
45 to 59
50
60 to 110
60.8
1 to 5
2
50 to 10000
700
Status
Unit
0 to 100
%
°C / °F
0 to 100
°C / °F
-
°C / °F
-
°C / °F
-
°C / °F
-
°C / °F
-
°C / °F
-
°C / °F
-
Unit
Description
-
Temperature
setpoints :
°F
Occupied Cooling
Stpt
°F
Unocc. Cooling Stpt 50
°F
Occupied Heating
Stpt
°F
Unocc. Heating
Stpt
°F
holiday setpoint
-
Humidity :
%
Occupied Humidity
Stpt
%
Occupied Humidity
DBand
%
Unoccupied
Humidity Stpt
%
Unoccupied
Humidity Db
-
Miscellaneous :
°F
Purge: OAT Low
Limit
°F
Purge: OAT High
Limit
min
Purge Duration
-
IAQ Setpoint
Displayed text*
Perecent Total Capacity
Control Point
Outdoor Air Temp
Supply Air Temperature
Space Temperature
Saturated Cond Tmp cir A
Saturated Cond Tmp cir B
Saturated Suction Temp cir A
Saturated Suction Temp cir B
Low Limit
High Limit
²²
50
89.6
89.6
50
75.2
50
75.2
50
75.2
10
80
10
50
10
80
10
50
45
59
60
110
1
5
50
10000
Description**
Perecent Total Capacity
Control point
Outdoor air temperature
Supply Air Temperature
Space Temperature
Saturated condensing temperature, circuit A
Saturated condensing temperature, circuit B
Saturated suction temperature, circuit A
Saturated suction temperature, circuit B