3-2. Method of installation

(1) Installation of Mounting Base
Please install a Mounting Base to "install holes" with two screws M3 which is more than 15mm length.
(See above)
! ! ! ! Warning
(2)Wiring
Please connect wires to holes of Wiring Terminal of Mounting Base (L, C).
Be sure to ground shielded of shield cable to the FG terminal of the control unit.
Branch Wiring is possible, and no polarity.
But do not bundle high voltage wires and electrical noise emitted wires with, or run them close to.
Caution
! ! ! !
! ! ! ! Warning
・Incorrect loading of the equipments can cause a malfunction, failure or
drop.
・Tighten the screw in the specified torque range.
・Under tightening can cause a drop, short circuit or malfunction.
・Over tightening can cause a drop, short circuit or malfunction due to
damage to the screw or he equipments and malfunction and fire.
Conformity wire is AWG18 - AWG26. Otherwise, use a wire and cause a
failure.
Tighten the wiring screw with the specified torque. If it's loose, it causes fire
and malfunction. (torque 0.5N・m: Reference value)
Conformity wire
18-26AWG
(Incase of Pin terminal, under φ2mm)
Strip length
4~5mm
ES1103
730110 K0
8