Detector Installation - Fenwal PSD Series Installation Instructions Manual

Detector bases (2- and 4-wire for smoke and electronic heat detectors)
Table of Contents

Advertisement

Detector
Base Model or
P/N
2-WIRE
2WRLT
2WRB
All Models
2WRB w/ LED
4WRB
70-201000-001
All models
70-201000-002
with MA-001
Mechanical
70-201000-003
Adapter Base
70-201000-005
Note: Minimum Alarm Impedance = 195 ohms; Maximum Alarm Impedance = 630 ohms.
CONTROL UNIT SELECTION

DETECTOR INSTALLATION

Spacing
Air Velocities
Model
CPD-7051
CPD-7051D
CPD-7054
CPD-7054D
PSD-7155
Mounting
Spacing
CID
Standby Voltage
(VDC)
FE51A
10.2 - 36.8
FE52A
10.2 - 36.8
FE53A
11.4 - 35.0
FE55A
11.4 - 35.0
N/A
16.3 - 30.8
FE01A
11.4 - 33.5
FE02A
11.4 - 33.5
FE03A
11.4 - 33.5
FE05A
11.4 - 33.5
Open Area (fpm)
0 - 300
0 - 300
0 - 300
0 - 500
0 - 300
Max. Alarm
Max. Standby
Current (mA)
Current (µA)
100
70
100
70
100
70
100
70
100
70
100
70
100
70
100
70
100
70
2
Model
PSD-7155P
PSD-7155D
PSD-7156
PSD-7157
PSD-7157D
www.fenwal-direct.eu
www.prevent-a-fire.eu
Typical Standby
Current (µA)
55
55
55
55
55
55
55
55
55
2
Open Area (fpm)
0 - 4000
0 - 300
0 - 300
0 - 300
0 - 4000

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Psd-7157Psd-7155Psd-7155pPsd-7155dPsd-7156Psd-7157d