Filling and venting the secondary side
!
Please note
Escaping liquids can lead to electrical defects.
Protect electrical components of the heat pump
from escaping liquids.
Fig. 49
Commissioning, inspection, maintenance
(cont.)
1. Open any non-return valves installed on site.
2. Check the pre-charge pressure of the expansion
vessel.
Technical guide
3. Fill (flush) and vent the secondary circuit:
Slightly open quick-action air vent valve, remains
open: See safety assembly, chapter "Connecting
the secondary circuit".
Open air vent valve DHW heating, remains open:
See the following chapter.
For venting, use lever to move the 3-way diverter
valve for "Heating/DHW heating" to its centre
position and click into place: See diagram.
!
4.
Please note
Leaking hydraulic connections lead to appli-
ance damage.
Check tightness of the internal and on-site
hydraulic connections.
In the event of leaks, switch off the appli-
ance immediately. Drain off liquid via the
drain valve. Check the seating of seal
rings. Always replace displaced seal rings.
5. Check system pressure. Top up with water if
required.
Minimum system pressure:
0.8 bar (80 kPa)
Permiss. operating pressure:
3 bar (0.3 MPa)