OPERATING PROCEDURE
6. Removing the thermistor <2-Phase Pipe> (TH6)
Note 1: When replacing thermistor <2-phase pipe> (TH6),
replace it together with thermistor <Ambient>
(TH7) since they are combined together.
Refer to procedure No.7 to remove the thermistor
<Ambient> (TH7).
7. Removing the thermistor <Ambient> (TH7)
Note 1: When replacing thermistor <Ambient> (TH7),
replace it together with thermistor <2-phase pipe>
(TH6), since they are combined together.
Refer to procedure No.6 to remove the thermistor
<2-phase pipe>(TH6).