<Outdoor unit operation monitor function>
[When optional part "A-Control Service Tool (PAC-SK52ST)" is connected to outdoor controller board (CNM)]
ON
1
2 3 4 5 6
<Digital indicator LED1 working details>
1
The tens digit : Operation mode
Display
Operation Model
O
OFF / FAN
C
COOLING / DRY *
H
HEATING
d
DEFROSTING
2
Display
Inspection unit
0
Outdoor unit
1
Indoor unit 1
2
Indoor unit 2
Display Contents to be inspected (When power is turned on)
63L connector(red) is open.
F3
63H connector(yellow) is open.
F5
2 connectors(63H/63L) are open.
F9
Indoor/outdoor communication error (Signal receiving error) (Outdoor unit)
E8
Indoor/outdoor communication error (Transmitting error) (Outdoor unit)
E9
EA
Miswiring of indoor/outdoor unit connecting wire, excessive number of indoor units (4 units or more)
Miswiring of indoor/outdoor unit connecting wire(converse wiring or disconnection)
Eb
Startup time over
EC
Incorrect connection
EE
Communication error except for outdoor unit
E0–E7
OCH651
All manuals and user guides at all-guides.com
The ones digit : Relay output
Display
0
1
2
3
4
5
6
7
8
A
Display
Contents to be inspected (During operation)
U1
Abnormal high pressure (63H operated)
U2
Abnormal high discharge temperature, high comp. surface temperature,
shortage of refrigerant
U3
Open/short of outdoor unit thermistors (TH4, TH33)
Open/short of outdoor unit thermistors (TH3, TH32, TH6, TH7 and TH8)
U4
U5
Abnormal temperature of heat sink
U6
Abnormality of power module
U7
Abnormality of superheat due to low discharge temperature
U8
Abnormality in outdoor fan motor
Ud
Overheat protection
Compressor overcurrent interruption (When Comp. locked)
UF
UH
Current sensor error
UL
Abnormal low pressure (63L operated)
UP
Compressor overcurrent interruption
P1–P8
Abnormality of indoor units
1 second
interval
ON
1
2 3 4 5 6
Warming-up
Compressor
4-way valve
Compressor
ON
ON
ON
ON
ON
ON
Solenoid valve
ON
ON
ON
ON
ON
ON
ON
ON
ON