Burner control units BCU 480 Technical Information · GB 6.1.2.8 Edition 06.07 • For pilot and main burners of unlimited capacity in intermittent or continuous operation pursuant to EN 746-2 • Automatic burner control unit, ignition transformer, indicators and operating...
The air valve control assists the furnace control for cooling, purging and capacity control tasks. The burner control units BCU 480 control, ignite and monitor The program status, the unit parameters and the level of the gas burners for intermittent or continuous operation. As a re- flame signal can be read directly from the unit.
Page 5
Application To reduce the installation and wiring costs, Elster Kromschröder offers an optional PROFIBUS-DP interface to transfer the ac- tivation signals and feedbacks so as to expand the remote servicing and diagnostics facilities. Bogie hearth forg- ing furnace in the...
UV sensor UVD 1 is used for continuous operation, UV sensor UVS for intermittent opera- tion. The BCU provides the cooling and purg- ing processes. 02–04 06–08 02–04 06–08 ϑ1 VR..L ϑ2 BCU 480 · Edition 06.07...
Pilot and main burners can be operated simultaneously. This reduces ϑ1 ϑ2 the time required by the main burner for starting up. BCU 480 The BCU provides the cooling and purg- ing processes. µC 02–04 06–08 06–08 ϑ1 VR..R ϑ2 BCU 480 · Edition 06.07...
This reduces the time required by the 50 51 main burner for starting up. The BCU provides the cooling and purg- ing processes. 02–04 06–08 06–08 ϑ1 ϑ2 IC 40 BCU 480 · Edition 06.07...
BCU 480 nalled. Pilot and main burners can be operated simultaneously. This reduces µC the time required by the main burner for starting up. BV+IC BCU 480 · Edition 06.07...
L1, N, PE controlling the air valve from the control system to the BCU 480..B1. In the oppo- site direction it sends operating status, the level of the flame signals and the current program status.
Certification The burner control unit BCU 480 is designed for applications pursuant to the Machinery Directive (98/37/EC). 3 .1 EC type-tested and certified pursuant to – Gas Appliances Directive (90/396/EC) in conjunction with EN 298 – Low Voltage Directive (73/23/EEC) in conjunction with EN 60730 –...
BCU 480..B1/1 2B 2A 1B 1A PROFIBUS-DP 4 .1 .2 BCU 480 . .B1 with Profibus For the explanation of symbols, see Legend. For further information on BCUs with Profibus, see Technical Information Bulletin “Burner control unit for Profibus-DP BCU 400..B1”.
4 .1 .3 BCU 480 . .P with 16-pin industrial plug connector The burner control unit BCU 480..P can be supplied with an industrial chassis plug (pursuant to VDE 0627). This 16-pin plug connector ensures fast connecting or disconnecting of units without any additional wiring required.
Page 15
16 15 14 8 11 10 ϑ ϑ 7 8 9 7 8 9 10 24 25 L1 (L1) N (L2) BCU 480 . .P with industrial plug connector For the explanation of symbols, see Legend. BCU 480 · Edition 06.07...
(display A1 ). signal V1” (terminal 4). Once the start-up Wait until signal ϑ1 has been applied, the BCU 480 min. burner pause time t has elapsed opens valve V1 and ignites the burner.
Page 17
In the event of flame failure: signal ϑ2 has been applied (terminal 21), fault lock-out the BCU 480 opens valve V2. The main burner is ignited by the pilot burner. If a The air valve can be set to open...
Page 18
4 start-up attempts or fault lock-out Function > BCU 480 program sequence Behaviour of the pilot burner in the event of flame failure during operation The air valve can be set to open Flame proving period If the flame fails during operation, either...
Purge Air valve No air flow in position X High temperature operation** X. X. * In Manual mode, two dots will blink on the display in program status 01 – 08 . ** Optionally available. BCU 480 · Edition 06.07...
0 – 25 s Air valve control 0; 1; 2; 3 Air valve can be activated externally on start-up 0; 1 Air valve closed/can be activated in the event of malfunction 0; 1 BCU 480 · Edition 06.07...
BCU can be scanned one after the other by repeatedly pressing the Reset/Information button (for 2 second). In the event of a fault, the BCU halts the program run, the display blinks and it then displays the cause of the fault in coded form. BCU 480 · Edition 06.07...
In parameter 03, it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00). Result: A flame simulation was detected during the waiting time or standby. BCU 480 · Edition 06.07...
For this purpose, we recommend a safety temperature monitor with twin thermocouple (DIN 3440). Sensor discontinuity, sensor short-circuit, failure of a component or mains failure must set the installation to a safe state. BCU 480 · Edition 06.07...
Page 24
UV control with UVD). The BCU switches off the burner once the DI input has been disconnected from the electrical power supply and restarts with flame simulation check (recommended in the case of UV control with UVS). BCU 480 · Edition 06.07...
Page 25
If no flame signal is present when High temperature operation is deactivated, the burner control unit performs a fault lock-out, regardless of parameter 33. Fault, pilot burner ϑ1 16-17 ϑ2 28-29 18-19 Fault, main burner ϑ1 16-17 ϑ2 28-29 18-19 BCU 480 · Edition 06.07...
It must be ensured in this case that the program sequence started matches the application. This parameter may be set in this way only if the burner can restart as intended in all operating phases. BCU 480 · Edition 06.07...
ϑ1 separately. ϑ2 The BCU 480 can also be used on indirectly ignited surface burners with end point monitoring. The pilot burner is switched off during the main burner safety Three different operating modes are possible: time t .
Start-up as in the illustration “Permanent pilot burner” with the difference being that the start-up signal for pilot and main burners is applied synchronously and that immediately after the flame proving period t , the main burner is started. BCU 480 · Edition 06.07...
ϑ2 The burner must have been switched off for at least 4 s be- fore start-up in order for the flame simulation check to be conducted correctly. BCU 480 · Edition 06.07...
After the pause time, the burner is started if the start-up signal (ϑ) is applied. The minimum burner pause time t serves to adapt the pro- gram sequence to the requirements of the application. BCU 480 · Edition 06.07...
Pilot burner Parameter 22 ϑ1 16-17 ϑ1 ϑ2 28-29 18-19 16-17 18-19 This indicates the safety time on start-up t for the main burner. This indicates the safety time on start-up t for the pilot burner. BCU 480 · Edition 06.07...
Parameter 25 28-29 18-19 ϑ1 16-17 ϑ2 28-29 18-19 Programmable time between 0 and 25 s. This time elapses before the BCU starts the next program step so as to give the flame time to stabilise. BCU 480 · Edition 06.07...
The display blinks and shows the cause of the fault. ϑ1 16-17 18-19 If no flame forms during start-up, a fault lock-out is performed after expiry of time t . The display blinks and shows the cause of the fault. BCU 480 · Edition 06.07...
Page 34
ϑ2 28-29 18-19 If no flame forms during the start-up of the main burner, a fault lock-out is performed after expiry of time t . The display blinks and shows the cause of the fault. BCU 480 · Edition 06.07...
The BCU cannot be reset by mains failure. The fault signalling contact does, however, open as soon as the mains voltage fails. See also parameter 32, Behaviour of the air valve in the event of a fault lock-out. BCU 480 · Edition 06.07...
Page 36
The precondition for a restart is that activation of the restart al- lows the burner to restart as intended (in all operating phases). In this case, it must be ensured that the program sequence started by the BCU matches the application. BCU 480 · Edition 06.07...
After a fault lock-out, the burner control unit can be reset, either with the button on the front panel or using an external button. Several burner control units can be reset in parallel using the external button. BCU 480 · Edition 06.07...
Page 38
The precondition for a restart is that activation of the restart al- lows the burner to restart as intended (in all operating phases). In this case, it must be ensured that the program sequence started by the BCU matches the application. BCU 480 · Edition 06.07...
– opens with valve V1 – opens with valve V2 – opens once the main burner has reached its operating position – Low fire over run time t after a normal shut-down BCU 480 · Edition 06.07...
In this case, activation of the air valve during burner start via ϑ2 input 23 must be prevented. 28-29 External control allows switchover between low fire and high fire during operation. 18-19 ϑ BCU 480..L VAS 1 VR..R BCU 480 · Edition 06.07...
Parameter 31 = 1: The air valve can be activated even dur- 00 A0 00 A0 ing start-up. ϑ1 These settings may be selected only if the burner can start with full air capacity. 16-17 ϑ2 28-29 18-19 ϑ BCU 480..L VAS 1 VAS..L BCU 480 · Edition 06.07...
ON/OFF via the ϑ input. ϑ1 The air valve can be activated externally via input 23 for cool- ing the burner in the start-up position/standby. 16-17 ϑ2 28-29 18-19 ϑ BCU 480..L VAS 1 VR..R BCU 480 · Edition 06.07...
ON/OFF via the ϑ input. ϑ1 The air valve can be activated externally via input 23 for cool- ing the burner in the start-up position/standby. 16-17 ϑ2 28-29 18-19 ϑ BCU 480..L VAS 1 VR..R BCU 480 · Edition 06.07...
On/Off control. Its must be ensured that GIK..B no excess gas occurs. VG..N The low fire over run time has an effect on the behaviour of the main burner only. VR..R Background: The pilot burner is only used in single-stage operation. BCU 480 · Edition 06.07...
Parameter 32 = 0: The air valve is closed in the event of a fault. It cannot be activated externally via terminal 23. Parameter 32 = 1: The air valve can be activated externally via input 23 even during a fault, e.g. for cooling. BCU 480 · Edition 06.07...
On units with air valve control, the air valve can be opened and closed repeatedly by pressing the button during operation. Manual mode can be terminated by switching off the BCU (On/Off button). BCU 480 · Edition 06.07...
= 3 s, 5 s or 10 s = Rated heat output = Ignition capacity The safety time of the automatic burner control unit depends on the burner type, the burner capacity and the respective application. BCU 480 · Edition 06.07...
9-pin D-Sub bus plug connector, IP 54 = /1* * If “none”, this specification is omitted. * If 1 start-up attempt, this specification is omitted. 1) Not in conjunction with PROFIBUS-DP = B1. = standard, = available. BCU 480-5/-3/1LW3GBC Order example BCU 480 · Edition 06.07...
50 m. Avoid external electrical interference. Install as far as possible from mains and ignition cables and interference from electro-magnetic sources. If possible, do not lay in a metal conduit. Several ionisation cables can be routed together. BCU 480 · Edition 06.07...
The minimum combustion time for the pilot burner is limited to the safety time on start-up (t Background: The pilot burner is only used in single-stage operation. BCU 480 · Edition 06.07...
Reset/Information button on the unit. Note the requirements of the Standards. For exceptions, see Standards. The burner malfunction must be remedied. The malfunction can not be remedied by changing the method of activation. BCU 480 · Edition 06.07...
). The max. number of start-ups per minute depends on the safety time t and the ignition transformer used: Ignition transformer TZI Max. start-ups/min. 5-15/100 5-15/100 5-15/100 7-25/20 7-25/20 7-25/20 7,5-12/100 7,5-12/100 7,5-12/100 7,5-20/33 7,5-20/33 7,5-20/33 BCU 480 · Edition 06.07...
Open BCU and screw on with four screws (Ø 4 mm, min. length 15 mm). From outside Screw on the closed unit to the rear with 4 self-tapping screws (enclosed). Otherwise, mount with external securing bars or fastening set (see Accessories). BCU 480 · Edition 06.07...
Page 54
The third gas valve (V3) and the air valve are activated simultaneously. During 02–04 06–08 06–08 purging/cooling, the gas valve (V3) is ϑ1 not activated. ϑ2 IC 40 BCU 480 · Edition 06.07...
ON signal), then disconnect the safety interlocks and finally Since EN 298 (1993) does not describe all functions of the BCU, switch off the system. the operator is responsible for ensuring that all parameters and functions are matched to the respective application. BCU 480 · Edition 06.07...
Document changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documenta- tion. If a replacement is ordered for a BCU with changed param- eters, refer to the protocol for details. BCU 480 · Edition 06.07...
This can be programmed using parameter 35. For further information, see brochure UVS. The burner control unit BCU..U is prepared for UV sensor UVD 1. This enables continuous operation. For further information, see Technical Information Bulletin UVD. BCU 480 · Edition 06.07...
Read the current parameters direct from the unit. Attention, paramètres modifiés ! Les informations figurant sur la plaque signalétique ne sont plus valables dans leur intégralité. Veuillez vous référer directement aux paramètres actualisés. BCU 480 · Edition 06.07...
Order No.: 74960414 Order No.: 74960422 9 .7 Radio interference suppressed electrode adapters Plug cap, 4 mm, interference-suppressed, Order No. 04115308. Straight adapter, 4 mm, interference-suppressed, Order No. 04115307. Straight adapter, 6 mm, interference-suppressed, Order No. 04115306. BCU 480 · Edition 06.07...
Output current: max. 2 A per output, but total current for valves and ignition transformer max. 2.5 A. Inherent current: Operation and fault signalling contacts: Signal “1” typ. 2 mA dry contact, max. 2 A, 264 V, not fused internally. BCU 480 · Edition 06.07...
Page 61
Input/Output safety circuit: All inputs/outputs marked with “ ” (see connection dia- gram) may be used for safety tasks. Weight: approx. 5 kg (11 lb) depending on version. BCU . .B1 External fuse: 12 A per zone. BCU 480 · Edition 06.07...
C: 2-digit 7-segment display. D: Mains switch to isolate the BCU on two poles from the mains. E: Reset/Information button to reset the system after a fault or to scan parameters on the display. � 4,5 mm 0.177" BCU 480 · Edition 06.07...
Safety time on start-up 3 s, 5 s or 10 s Safety time during operation < 1 s or < 2 s Ignition time 2 s, 3 s or 6 s Flame simulation delay time 25 s Flame proving period 0 – 25 s BCU 480 · Edition 06.07...
The duration of the ignition time is either 2, 3 or 7 seconds depending on safety time t selected. If the flame fails during operation, the valve outputs are dis- connected within the safety time t BCU 480 · Edition 06.07...
It remains open until the burner is switched – to control the burner capacity in ON/OFF mode and in off again by a normal shut-down or fault lock-out. High/Low mode when using a pneumatic air/gas ratio control system. BCU 480 · Edition 06.07...