Service
Service
After the TLM has been installed, the only additional
maintenance or service necessary is changing the
batteries.

Replace Batteries

WARNING
Fire and Explosion Hazard
Sparking can occur when changing batteries. Only
replace the batteries in a non-hazardous location
away from flammable fluids and fumes.
NOTE: After battery placement, activate the TLM with a
magnet (see Activation, page 2), to synchronize the
TLM internal clock to maintain scheduled TLM
readings.
1. Remove the TLM from the tank by unscrewing it
from the opening.
2. Remove the four (4) screws that keep the case
together (F
. 6).
IG
F
. 6
IG
8
3. Verify that the device is right side up before opening
to prevent the batteries from falling out (F
Top
Bottom
F
. 7
IG
4. Replace the four (4) C-cell Alkaline batteries
(F
. 8).
IG
Negative (-)
F
. 8
IG
. 7).
IG
Positive (+)
3A8551B