Videographic Recorders
SM1000 and SM2000

2 Installation

2.1 General

Note. Ensure that permission has been granted for
installation of new devices on the network. If in doubt,
consult the System Administrator before connecting the
instrument.
To connect the instrument into an Ethernet network, use a single
network cable to link it to the network hub. The connection is
made using a standard RJ45 connector at the rear of the unit on
module C – see Fig. 2.1.
Continuity/Receive LED
(Green)
Fig. 2.1 Ethernet Connector
Table 2.1 shows the signals carried by each pin of the
connector.
Pin Number
1
2
3
4
5
6
7
8
TD = Transmit Data
Table 2.1 Ethernet Connector Signals
Note. To prevent signal degradation, the maximum cable
length between 10BaseT network devices is limited to
100m. If longer cable runs are required between devices,
repeaters or gateways must be used to boost signal
strengths.
IM/SMENET Issue 4
Transmit LED (Orange)
RJ45 Connector
(Type 5)
Signal
TD+
TD–
RD+
Unused
Unused
RD–
Unused
Unused
RD = Receive Data
The instrument uses standard Ethernet and web standards and
can be connected in a number of network configurations
including:
Direct connection to a computer – see Fig. 2.2
Connection to a network hub – see Fig. 2.4
Connection to a dial-up router – see Fig. 2.5
Connection to an internet gateway – see Fig. 2.6
2.2 Direct Connection to a Computer –
Figs. 2.2 and 2.3
Note. A crossover cable is required for this configuration.
See Fig. 2.3 for connection details.
Crossover
Cable
SM1000/SM2000
Fig. 2.2 Direct Connection
TD+
TD–
RD+
RD–
Fig. 2.3 Crossover Cable Connections
2 Installation
PC
TD+
TD–
RD+
RD–
3