Electrical - Lennox ELITE Series Installation Instructions Manual

Gas furnace downflow air discharge
Table of Contents

Advertisement

Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a
venting system commonly run with separate gas applianc-
es, the venting system is likely to be too large to properly
vent the remaining attached appliances. Conduct the fol-
lowing test while each appliance is operating and the oth-
er appliances (which are not operating) remain connected
to the common venting system. If the venting system has
been installed improperly, you must correct the system as
indicated in the general venting requirements section.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed
into operation could result in carbon monoxide poisoning
or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1 - Seal any unused openings in the common venting
system.
2 - Inspect the venting system for proper size and
horizontal pitch. Determine that there is no blockage,
restriction, leakage, corrosion, or other deficiencies
which could cause an unsafe condition.
3 - Close all building doors and windows and all
doors between the space in which the appliances
remaining connected to the common venting system
are located and other spaces of the building. Turn on
clothes dryers and any appliances not connected to
the common venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts,
so they will operate at maximum speed. Do not
operate a summer exhaust fan. Close fireplace
dampers.
4 - Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that
the appliance operates continuously.
5 - After the main burner has operated for 5 minutes,
test for leaks of flue gases at the draft hood relief
opening. Use the flame of a match or candle.
6 - After determining that each appliance connected to
the common venting system is venting properly, (step
3) return all doors, widows, exhaust fans, fireplace
dampers, and any other gas-burning appliances to
their previous mode of operation.
7 - If a venting problem is found during any of the
preceding tests, the common venting system must
be modified to correct the problem. Resize the
common venting system to the minimum vent pipe
size determined by using the appropriate tables in
Appendix G. (These are in the current standards of
the National Fuel Gas Code ANSI Z223.1.

Electrical

ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
Electrostatic discharge can affect electronic
components. Take precautions to neutralize
electrostatic charge by touching your hand
and tools to metal prior to handling the
control.
Electric Shock Hazard. Can cause injury or
death. Unit must be properly grounded in
accordance with national and local codes.
Fire Hazard. Use of aluminum wire with this product may
result in a fire, causing property damage, severe injury
or death. Use copper wire only with this product.
The unit is equipped with a field make-up box on the left
hand side of the cabinet. A field-provided make-up box
can be installed on the exterior of the right side of the fur-
nace to facilitate installation. If the make-up box is moved
to the right side, clip the wire ties that bundle the wires to-
gether and install on the outside of the cabinet. See figure
52. The excess wire must be pulled into the blower com-
partment. Secure the excess wire to the existing harness
to protect it from damage.
Refer to figure 53 for field wiring and troubleshooting.
EXTERIOR MAKE-UP BOX
(FIELD PROVIDED RIGHT SIDE)
The power supply wiring must meet Class I restrictions.
Protected by either a fuse or circuit breaker, select circuit
protection and wire size according to unit nameplate.
NOTE - Unit nameplate states maximum current draw.
Maximum Over-Current Protection allowed is 15 AMP.
Holes are on both sides of the furnace cabinet to facilitate
wiring. Holes are on both sides of the furnace cabinet to
facilitate wiring.
Page 35
CAUTION
WARNING
WARNING
MAKE-UP
BOX
OUTSIDE
CABINET
Right Side
Figure 52