power supply through a fuse dependent by
the total amount of the line's power load.
3. It is suggested to check every month the
indication LED for battery charging, and by
pushing instantly the TEST button to check
the emergency circuit and the lamps. If the
luminaire does not light
4. It is suggested to check every 6 months the
minimum autononous duration by
disconnecting the mains power supply.
Count the time that the lamps light and in
case of less time than the minimum
autonomous duration the batteries must be
replaced. If the measured time is
considerably less than the minimum
autonomous duration
The replacement of the battery and the light
source must be done using parts of the
same type, by the manufacturer or by a
competent person.
5.
In case of inactive use for a period greater
than 2 months, disconnect the battery by
pulling out the battery's connector.
6. I s not allowed to discard batteries in to
t i
common trash bins, they must be
discarded only
points. Do not incinerate.
(*) Non Maintained operation: The luminaire lights its illumination source, only in power supply's
failure.
Maintained operation: The luminaire lights its illumination source, when it is powered by the mains
power supply or not.
The light source contained in this luminaire shall only be replaced by the manufacturer, or
his agent, or a similar qualified person.
NOTE! The light source is non-user replaceable.
Manufacturer
Manufacturer
Voltage Range
Nominal Power
Connections
Temperature (tc)
INDICATION LED STATUS (with the mains power supply connected)
CHARGE
Disconnected battery / not charging
Charged battery
Battery under charge
Indicator OFF
Page 2 from 3
contact the installer.
contact the installer.
in battery recycling
LED MODULE CHARACTERISTICS
Cable connection between main pcb and led module
Indicator Blinking
Indicator ON
Battery replacement
It can be done only by a competent person
and after the mains interruption.
1. Follow the step 2 of the installation
procedure.
2. Disconnect the cables and remove the old
battery.
3. Connect the new battery with the same type
(step 3 of the installation procedure) and
place it in the position of the old one.
4. Follow the step 6 of the installation
procedure and power the device.
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
0: Non Maintained (*)
A:
Including test device
*180: 3 hours duration
GRL-29/WP
Olympia Electronics S.A.
2002163
20-25V
5.5W
60 °C max. across the board
POWER
No mains power supply
Normal operation mode