Configuring 
A standard configuration kit includes a USB-RS485 converter, fixed flow regulator, gas
 
 
tubing with applicators, and a software pack. Please contact your Seller for more
 
 
information. 
Detectors- transmitters E2658 share all functionalities of the PluraSens® multifunctional
 
platform. The features and options include: 
Digital output change rate-limiting filter 
Digital integrating (averaging) filter 
Free assignment of each analog output to the chosen parameter 
Flexible setting of analog output scales for each output 
Output zero and slope adjustment for calibration 
Free assignment of each of two relays to the chosen parameter 
Several relay control logic modes 
Switch delays and minimum on/off state durations for each relay 
 
The output scales can be changed by Modbus commands by using the configuration
 
 
software and the standard kit (see Modbus RTU Communication).  
Return to default settings 
To reset the device's Slave ID, baud rate, and stop bit numbers to factory settings, proceed
 
 
 
as follows: 
1. De-energize the device   
2. Connect the X6 jumper 
3. Turn on the device 
4. De-energize the device 
5. Disconnect the X6 jumper
6. Turn on the device 
 
 
 
 
   
 
 
 
 
 
 
 
 
 
 
 
 
   
 
 
 
 
 
 
 
 
 
 
 
 