Daikin DBG Series Installation Instructions Manual page 12

Packaged gas / electric unit 7.5-12.5 ton belt drive
Table of Contents

Advertisement

NOTE: CHECK TRANSFORMER TO MATCH
THE CORRECT VOLTAGE TAP WITH LINE VOLTAGE
control box
note: depending on the options installed, the
location of the components may vary in some
models.
Failure of unit due to operation on improper
line voltage or with excessive phase unbalance
constitutes product abuse and will void your
warranty and may cause severe damage to the
unit electrical components.
Areas Without Convenience Outlet
It is recommended that an independent 115V power source
be brought to the vicinity of the roof top unit for portable
lights and tools used by the service mechanic.
NOTE: Refer to local codes for requirements.
These outlets can also be factory installed.
WARNING
Units installed on Roof Tops
Main power and low voltage wiring may enter the unit
through the condenser end of unit or through the roof curb.
Install conduit connectors at the desired entrance locations.
External connectors must be weatherproof. All holes in the
unit base must be sealed (including those around conduit
nuts) to prevent water leakage into building. All required
conduit and fittings are to be field supplied.
Supply voltage to roof top unit must not vary by more than
10% of the value indicated on the unit data plate. Phase
voltage unbalance must not exceed 2%. Contact your
local power company for correction of improper voltage or
phase unbalance.
24.4
LINE VOLTAGE L1, L2, L3
LOW VOLTAGE ENTRANCE
GROUND LUG
SUPPLY
RETURN
electrical entrance and thru curb
Low Voltage Control Wiring
1. A 24V thermostat must be installed for unit operation
unless the DDC controls option has been installed.
2. Locate thermostat or remote sensor in the conditioned
space where it will sense average temperature. Do
not locate the device where it may be directly exposed
to supply air, sunlight or other sources of heat. Follow
installation instructions packaged with the thermostat.
12
HIGH VOLTAGE ENTRANCE
(REMOVE PLUG)
20-3/4
(bottom view of unit)
THRU THE CURB

Hide quick links:

Advertisement

Table of Contents
loading