Daikin DBG Series Installation Instructions Manual page 11

Packaged gas / electric unit 7.5-12.5 ton belt drive
Table of Contents

Advertisement

HIGH VOLTAGE!
To avoid personal injury or death
due to electrical shock, do not
tamper with factory wiring. The
internal power and control wiring
of these units are factory-installed
and have been thoroughly tested
prior to shipment. Contact your
local representative if assistance is
required.
To prevent damage to the wiring, protect wiring
from sharp edges. follow national electrical
code and all local codes and ordinances. Do
not route wires through removable access
panels.
Conduit and fittings must be weather-tight to
prevent water entry into the building.
For unit protection, use a fuse or HACR circuit breaker that
is in excess of the circuit ampacity, but less than or equal
to the maximum overcurrent protection device. DO NOT
EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE
SHOWN ON UNIT DATA PLATE.
All line voltage connections must be made through
weatherproof fittings. All exterior power supply and ground
wiring must be in approved weatherproof conduit.
The main power supply wiring to the unit and low voltage
wiring to accessory controls must be done in accordance
with these instructions, the latest edition of the National
Electrical Code (ANSI/NFPA 70), and all local codes and
ordinances.
The main power supply shall be three-phase, three wire.
The unit is factory wired for the voltage shown on the unit's
data plate.
NOTE: If supply voltage is 208V, lead on primary of
transformer(s) must be moved from the 230V to
the 208V tap. Refer to wiring diagram on unit for
details.
WARNING
CAUTION
CAUTION
Main power wiring should be sized for the minimum circuit
ampacity shown on the unit's database. Size wires in
accordance with the ampacity tables in Article 310 of the
National Electrical Code. If long wires are required, it
may be necessary to increase the wire size to prevent
excessive voltage drop. Wires should be sized for a
maximum of 3% voltage drop.
To avoid risk of property damage, personal
injury or fire, use only copper conductors.
To prevent improper and dangerous operation
due to wiring errors, label all wires prior to
disconnection when servicing controls. Verify
proper operation after servicing.
NOTE: A weather-tight disconnect switch, properly
sized for the unit total load, must be field or
factory installed. An external field supplied
disconnect may be mounted on the exterior panel.
Ensure the data plate is not covered by the field-supplied
disconnect switch.
• Some disconnect switches are not fused. Protect the
power leads at the point of distribution in accordance
with the unit data plate.
• The unit must be electrically grounded in accordance
with local codes or, in the absence of local codes,
with the latest edition of the National Electrical Code
ANSI/NFPA 70, and/or the Canadian Electrical Code,
CSA C22.1, Part 1. A ground lug is provided for this
purpose. Do not use the ground lug for connecting a
neutral conductor.
• Connect power wiring to the electrical power block
located within the main control box.
11