Samsung VRF DVM S Water Technical Data Book page 20

Hide thumbs Also See for VRF DVM S Water:
Table of Contents

Advertisement

2. Specification
NOTE
• Specification may be subject to change without prior notice.
1) Cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB, Inlet water temperature : 30°C, Equivalent refrigerant piping :
7.5m, Level differences : 0m
2) Heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB, Inlet water temperature : 20°C, Equivalent refrigerant piping :
7.5m, Level differences : 0m
3) Sound power level is an absolute value that a sound source generates.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound values are obtained in an anechoic room.
- Sound values of multi comvination are theoretical values based on sound results of individual installed units.
4) Heating capacityes are based on;
- Indoor temperature : 20°C DB, 15°C WB, Inlet water temperature : 10°C, Outlet water temperature : 7°C,
Equivalent refrigerant piping : 7.5m, Level differences : 0m
5) These products contain R410A(GWP=2,088) which is fluorinated greenhouse gas.
6) Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit
capacity. 0.5 × ∑(Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × ∑(Outdoor unit
capacity)
7) You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor
unit is set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be
assigned from indoor unit address was assigned from 64~79, E201 error will occur.0~63. If the If the indoor
unit address was assigned from 64~79, E201 error will occur.
20

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents