Step 6 Connecting the refrigerant pipe

◆ AJ040/050TXJ2KG
1 Piping outside diameter
Indoor unit
Out unit
AR07/09/12********,
AJ040TXJ2KG 1,220-240, 50
AJ026/035TN*D*G
AR07/09/12********,
AJ016/020/026
/035TN*D*G
AJ050TXJ2KG 1,220-240, 50
AR18********,
AJ052TNJDKG
NOTE
• This product requires no additional refrigerant charge
up to the maximum allowable pipe length.
Maximum allowable refrigerant charge amount
AJ040TXJ2KG/EU
AJ050TXJ2KG/EU
• AJ040TXJ2KG Outdoor unit cannot be connected to
the following indoor unit combination.
-AJ0**TNNDKG/AJ0**TNLDEG
Make at least one round:
It will reduce noise and vibration
2 Piping length and the height
1 Room
max
length
Dimension
20m
Composition
A,B
Outside
Power supply
diameter
Ø, V, Hz
Liquid
Gas
1/4"
3/8"
3/8"
1/4"
1/2"
(h) (H)
A
B
Main power switch
980 g
1180 g
2 Room
Max height
Max height
total max
between
between
length
indoor unit
indoor units
& outdoor
unit
30m
15m
7.5m
A+B
(H)
(h)
◆ AJ052/068TXJ3KG
1 Piping outside diameter
Indoor unit
Out unit
AR07/09/12********,
AJ016/020/026
AJ052TXJ3KG
/035TN*D*G
AJ068TXJ3KG
AR18********,
AJ052TN*D*G
Main power switch
NOTE
• AJ052TXJ3KG Outdoor unit cannot be connected to
the following indoor unit combination.
-AJ052TNNDKG/AJ052TNMDEG
• AJ068TXJ3KG Outdoor unit cannot be connected to
the following indoor unit combination.
-AJ***TNJDKG
2 Piping length and the height
1 Room
max
length
Dimension
25m
Composition
A,B,C
Make at least one round:
It will reduce noise and vibration
Outside
Power
diameter
supply Ø,
V, Hz
Liquid Gas
3/8"
1,220-240,
1/4"
50
1/2"
(h) (H)
C
A
B
3 Room
Max height
Max height
total max
between
between
length
indoor unit
indoor units
& outdoor
unit
50m
15m
7.5m
A+B+C
(H)
(h)
English
19