7.2

Example of an electrical system without heater

➤ Do not invert the neutral with the phase in the
electrical supply line.
➤ Check that the electrical supply of the burner
WARNING
corresponds to that shown on the identifica-
tion label and in this manual.
➤ The section of the conductors must be at
least 1mm
local guidelines and laws).
Test the burner by checking the shutdown of the
burner by opening the thermostats and the lockout
by darkening the photoresistance.
WARNING
➤ If the hood is still present, remove it and pro-
ceed with the electrical wiring according to
the wiring diagrams.
➤ Use flexible cables in compliance with the EN
CAUTION
60 335-1 standard.
20068634
Electrical system
~ 50Hz - 230 V
General
switch
T4A
White
CARRIED OUT
IN THE FACTORY
2
. (Unless otherwise required by
TO BE DONE BY
THE INSTALLER
CONTROL BOX
Black
White
Blue
Key (Fig. 18)
C
Capacitator
E
Ignition electrodes
F
Flame detector
MV
Fan motor
P
Short circuit socket
RS
Remote reset
SB
Remote lock-out signal (230V - 0.5A max)
TB
Burner earth
TL
Heat request thermostat
TS
Safety thermostat
V
Oil valve
XP5
5- pole socket
X5
5 pin plug
18
GB
20068692
Fig. 18