Huawei FusionServer Pro 1288X V5 Server
Technical White Paper
Category
Altitude
Corrosive gaseous
contaminant
Particle contaminant
Acoustic noise
Issue 02 (2020-04-20)
Specifications
● Operating altitude ≤ 3050 m (10006.44 ft)
– If the server complying with ASHRAE Class A2 is
used in a place above 900 m (2952.76 ft), the
highest operating temperature decreases by 1°C
(1.8°F) for every increase of 300 m (984.25 ft).
– If the server complying with ASHRAE Class A3 is
used in a place above 900 m (2952.76 ft), the
highest operating temperature decreases by 1°C
(1.8°F) for every increase of 175 m (574.15 ft).
– If the server complying with ASHRAE Class A4 is
used in a place above 900 m (2952.76 ft), the
highest operating temperature decreases by 1°C
(1.8°F) for every increase of 125 m (410.10 ft).
● HDDs cannot be used at an altitude of over 3000 m
(9842.4 ft).
Maximum corrosion product thickness growth rate:
● Copper corrosion rate test: 300 Å/month (meeting
level G1 requirements of the ANSI/ISA-71.04-2013
standard on gaseous corrosion)
● Silver corrosion rate test: 200 Å/month
● The equipment room environment meets the
requirements of ISO 14664-1 Class 8.
● There is no explosive, conductive, magnetic, or
corrosive dust in the equipment room.
NOTE
It is recommended that the particulate pollutants in the
equipment room be monitored by a professional organization.
The declared A-weighted sound power levels (LWAd)
and declared average bystander position A-weighted
sound pressure levels (LpAm) listed are measured at
23°C (73.4°F) in accordance with ISO 7779 (ECMA 74)
and declared in accordance with ISO 9296 (ECMA 109).
● Idle:
– LWAd: 5.92 Bels
– LpAm: 42.3 dBA
● Operating:
– LWAd: 6.14 Bels
– LpAm: 46.3 dBA
NOTE
Actual sound levels generated during operation vary
depending on server configuration, load, and ambient
temperature.
Copyright © Huawei Technologies Co., Ltd.
6 Product Specifications
42