3.3.3 Minimum distances from the walls and ventilation

The UPS must be so installed as to ensure its serviceability and to allow a correct air flow as
much as possible.
With regard to the minimum distances from the walls, for all of the UPS sizes the same
installation conditions apply as indicated in the table below.
Picture 5 – Minimum distances from the walls
The table below shows the air volume required for an optimal ventilation and cooling of the
UPS.
Power (kVA)
Air volume (m
22
OMD36055 REV. D
Installation and start-up of UPS Keor Hp 200-300kVA
Installation et démarrage de l'UPS Keor Hp 200-300 kVA
Installazione e avviamento UPS Keor Hp 200-300kVA
A (mm)
B (mm)
1000
700
200
3
/h)
3500
D (mm)
50
250
300
4100