Radiant Sizing:
Estimating Radiant Tubing
6" OC
Qty = FT
of space x 2
2
12" OC
Qty = FT
of space x 1.2
2
Estimating BTUH for Radiant
Floor Warming = 15-20 btuh/ft
Floor Heating = 35-50 btuh/ft
Expansion Tank Quick Sizer
Finned
Boiler Output
Baseboard
25,000
50,000
75,000
100,000
125,000
150,000
175,000
200,000
250,000
300,000
Buffer Tank Sizing
Minimum
Tank
= Boiler Run Time x (Min Boiler Firing Rate - Smallest Zone)
Volume = 500 x ∆T
Pool Sizing
Pool Capacity (gallons):
Circular Pool = Avg. Depth x Diameter
Rectangular Pool = Avg. Depth x Length x Width x 7.5
BTUH Requirement:
Pool Capacity x 8.34 x Temp Rise
BTUH =
Hours to Heat Pool
Temp. Difference
between pool temp and
ambient air temp (°F)
BTUH/Ft
2
Air Handler/
Unit Heater
15
15
15
15
30
30
30
30
30
60
30
60
60
60
60
90
60
90
90
30V
x 5.9
2
10°
15°
105
158
Cast
Cast Iron
Radiator
Baseboard
15
15
30
30
30
60
60
60
60
90
90
90
30V
30V
30V
30V
30V
40V
30V
40V
20°
25°
210
263
30°
368
71