Technical Specifications; Power Supply Specifications; Failsafe Relay Specifications - Siemens RUGGEDCOM RX1511 Installation Manual

Simatic net
Hide thumbs Also See for RUGGEDCOM RX1511:
Table of Contents

Advertisement

Technical Specifications

This section provides important technical specifications related to the device.
5.1

Power Supply Specifications

Note
When determining cable lengths, make sure the minimum input voltage for the pow-
er supply is provided at the power source.
Power Sup-
a
Power consumption varies based on the device configuration. A typical RUGGEDCOM RX1511 chassis
will consume approximately 35 W of power.
b
(T) denotes time-delay fuse.
5.2

Failsafe Relay Specifications

Maximum Switching Voltage
a
Inductive load R/L = 7 ms
b
Resistive load
RUGGEDCOM RX1511
Installation Manual, 07/2019, C79000-G8976-1056
Input Range
ply Type
Min
88 VDC
HI
85 VAC
88 VDC
HIP
85 VAC
24
13 VDC
24P
48
36 VDC
48P
12
9 VDC
12P
30 VDC
125 VDC
250 VAC
Internal
Fuse Rating
Max
300 VDC
3.15 A(T)
264 VAC
300 VDC
3.15 A(T)
264 VAC
36 VDC
10 A(T)
72 VDC
3.15 A(T)
15 VDC
12 A
Rated Switching Current
5 A
a
b
0.1 A
, 0.15 A
6.25 A
Maximum
Power Con-
a
sumption
b
65 W
b
65 W
b
63.5 W
b
60 W
67 W
Isolation
2800 VDC for 1 minute be-
tween coil and contacts
5
Insulation
2800 VDC
for 1 minute
1500 VDC
for 1 minute
1500 VAC or
2121 VDC
for 1 minute
43