Omron E5*N Series Solutions Manual For Faqs page 20

Digital temperature controllers basic type
Hide thumbs Also See for E5*N Series:

Advertisement

Simplicity on the Worksite
Setting Temperature Alarms
Step 2 Setting Alarm Parameters
1
Setting the Alarm Type
You set this parameter in the Initial Setting Level. The parameter is set to 2 (Upper-limit Alarm) by default.
1
Turn ON the power supply.
2
Press the
Key for at least 3 seconds.
Press the
for at least 3 seconds.
3
Change the parameter with the
Press the
several times to display
alt1 (ALT1).
4
Set the parameter with the
Set the alarm type number that
you selected on page 4-3.
If required, use the
and set alarm type numbers for alt2 (ALT2) (Alarm 2) and alt3 (ALT3) (Alarm 3).
(The number of alarms that is supported depends on the model of Temperature Controller.
Some of the alarm parameters may not be displayed.)
(When finished, press the
4-6
Solutions Guide for FAQs: E5@N
Operating Display
(Level) Key
Initial Setting Level
Key.
Initial Setting Level
(Mode) Key
Keys.
Initial Setting Level
(Mode) Key and the
(Up and Down) Keys to repeat steps 3 and 4
(Level) Key for at least 1 second to return to the operation display.)
←Flashes 3 times.
←in-t (IN-T) will be displayed to
show that the Initial Setting Level
has been entered.
←alt1 (ALT1): Indicates the Alarm 1
parameter.
←Default setting is 2 (Upper-limit
Alarm).
Change the set value with
the
(Up and Down)
Keys.