8 FLEX Ex 85...253V AC In/Quad-Ex DC Out Power Supply

Electrostatic Charge

Protect the system against electrostatic charge. Post a sign near this module.
Attention! Avoid electrostatic charge.
ATENÇÃO! PREVENIR CONTRA O ACÚMULO DE
CARGA ELETROSTÁTICA
For your convenience, a sign that can be cut out and posted is included on the
last page of these installation instructions.
European Hazardous Location Approval
The following applies to products marked
• Are Equipment Group II, Equipment Category 2, and comply with
the Essential Health and Safety Requirements relating to the design
and construction of such equipment given in Annex II to Directive
2014/34/EU. See the EC Declaration of Conformity at
http://www.rockwellautomation.com/products/certification
for details.
• The type of protection is "Ex de [ib] IIC T4 Gb" according
to EN 60079-11.
• Comply to Standards EN 60079-0:2012, EN 60079-1:2007,
EN 60079-7:2007, and EN 60079-11:2012, reference certificate
number DMT 02 ATEX E 253 X.
• Are intended for use in areas in which explosive atmospheres caused
by gases, vapors, mists, or air are likely to occur occasionally. Such
locations correspond to Zone 1 or 2 classification according to ATEX
directive 2014/34/EU.
Publication
1797-IN533-EN-P - August 2017
II 2 G