Section 3-3: Installing a Wall Mounted Vent System

This section applies to installations where the shortest possible vent
run is through the wall. Refer to Appendix A - Power Vent locations,
to ensure the planned Power vent location is acceptable. Refer to the
table below for vent run requirements. Please note, images are shown
without screens for clarity purposes. However, your fireplace should
not be operated without proper installation of screens.
Selection of components and details of venting lay out should
adhere to the following guidelines:
Ensure the maximum vent run does not exceed 100'
Ensure the number of 90° elbows does not exceed 6
Ensure the number of 45° elbows does not exceed 12
One Elbow Layout
V
V1
R320ST, R420ST
R520ST, R620ST
Figure 6.d Straight Horizontal, Top Vent, Wall mounted power vent.
Multi-Elbow Installations
H1
R320ST, R420ST
V1
R520ST, R620ST
Figure 6.f Multi-Elbow, Top Vent, Wall mounted power vent.
XG0231 - 061120
H
H1
Max. #
MAX V1+H1
Elbows
100'
6
100'
6
V3
H2
V2
MAX V1+H1+
Max. #
V2+H2+V3+H3
Elbows
100'
6
100'
6

Downward Vertical Venting

MAX V1+H1+
D+H2+V3
R320ST, R420ST
40'
R520ST, R620ST
40'
H1
H1
V
V1
Figure 6.g Multi-Elbow with downward vent run, Top Vent, Wall mounted power vent.
Installation
Max. #
Elbows
6
6
D
D = 6' Max
H2
H2
13