Toshiba MMY-MAP0806FT8P-E Installation Manual page 88

Air conditioner (multi type)
Hide thumbs Also See for MMY-MAP0806FT8P-E:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
<Corrective trial>
q Start operation
1
Set the rotary switches on the interface P.C. board of the header outdoor unit as below.
When in "COOL" mode: SW01=[2], SW02=[5], SW03=[1].
When in "HEAT" mode: SW01=[2], SW02=[6], SW03=[1].
When in "FAN" mode: SW01=[2], SW02=[9], SW03=[1].
2
Push and hold SW04 for more than 2 seconds.
NOTE
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after turning the power on or stopping running.
q Stop operation
1
Set the rotary switches on the interface P.C. board of the header unit back:
SW01 to [1], SW02 to [1] and SW03 to [1].
173-EN
1117701001-EN.indd 87
1117701001-EN.indd 87
– 87 –
7-segment display
[A]
[B]
[C
]
[
]
[H
]
[
]
[F
]
[
]
7-segment display
[A]
[B]
[C
]
[
- C
]
[H
]
[
- H
]
[F
]
[
- F
]
7-segment display
[A]
[B]
[U1]
[
]
Interface PC board
SW04
Push switch
D600 D601 D602 D603 D604
7-segment
display [A]
SW01 SW02 SW03
Rotary switches
SW05 SW15
Push switch
7-segment
display [B]
174-EN
2/26/2559 BE 11:48 AM
2/26/2559 BE 11:48 AM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents