Adding refrigerant
After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of
refrigerant.
Calculation of additional refrigerant charge amount
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipes at the local site.
For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
NOTE
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without
additional refrigerant.
Outdoor unit type
MAP080
Charging amount (kg)
Additional refrigerant
=
Real length of liquid pipe
charge amount at local site
Table 1
Liquid pipe dia. (mm)
6.4
Additional refrigerant amount / 1 m
0.025
liquid pipe (kg/m)
139-EN
1117701001-EN.indd 70
1117701001-EN.indd 70
MAP100
MAP120
MAP140
MAP160
MAP180
MAP200
11.0
Corrective amount of
Additional refrigerant
refrigerant depending on HP
×
charge amount per 1 m
×
1.3
+
of co-operating outdoor units
liquid pipe (Table 1)
(Table 2)
9.5
12.7
15.9
19.1
0.055
0.105
0.160
0.250
Table 2
Model name of
Equivalent
outdoor unit
HP
MMY-
8HP
MAP0806*
10HP
MAP1006*
12HP
MAP1206*
14HP
MAP1406*
16HP
MAP1606*
18HP
MAP1806*
20HP
MAP2006*
22HP
AP2216*
24HP
AP2416*
26HP
AP2616*
28HP
AP2816*
30HP
AP3016*
32HP
AP3216*
34HP
AP3416*
36HP
AP3616*
38HP
AP3816*
22.2
40HP
AP4016*
0.350
42HP
AP4216*
44HP
AP4416*
46HP
AP4616*
48HP
AP4816*
50HP
AP5016*
52HP
AP5216*
54HP
AP5416*
Charging of refrigerant
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the
liquid side.
• If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and
gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas
side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
– 70 –
Combination of outdoor unit
MMY-
Unit 1
Unit 2
Unit 3
MAP0806*
-
-
MAP1006*
-
-
MAP1206*
-
-
MAP1406*
-
-
MAP1606*
-
-
MAP1806*
-
-
MAP2006*
-
-
MAP1206*
MAP1006*
-
MAP1406*
MAP1006*
-
MAP1406*
MAP1206*
-
MAP1406*
MAP1406*
-
MAP1606*
MAP1406*
-
MAP1806*
MAP1406*
-
MAP1806*
MAP1606*
-
MAP1806*
MAP1806*
-
MAP2006*
MAP1806*
-
MAP2006*
MAP2006*
-
MAP1406*
MAP1406*
MAP1406*
MAP1606*
MAP1406*
MAP1406*
MAP1806*
MAP1406*
MAP1406*
MAP1806*
MAP1606*
MAP1406*
MAP1806*
MAP1806*
MAP1406*
MAP1806*
MAP1806*
MAP1606*
MAP1806*
MAP1806*
MAP1806*
Corrective of
refrigerant
(kg)
2
3
8
10
12
14
15
6
8
12
12
14
15
16
18
22
24
14
15
16
17
18
20
22
140-EN
2/26/2559 BE 11:48 AM
2/26/2559 BE 11:48 AM